Installation,
Wiring,
and
Specifications
2--30
Installation, Wiring, and Specifications
DL105 PLC User Manual, 3rd Edition
The F1--130AR has a +24V supply output to power external devices. The output is
rated at 0.5 Amperes, and includes short-circuit protection and full isolation from
internal CPU circuitry. These features make it ideal for powering sensors, solenoids,
and other field devices. In fact, it can be used as the DC supply for loads in the relay
output circuits. Be sure the combined load currents do not exceed 0.5 A. Note that on
the F1--130AR, the +24V auxiliary output is not high enough to power its input
circuits (input ON threshold is 90VDC).
External Power Requirements
100 -- 240 +10% --15%
Communication Port
K--Sequence, 9600 baud, 8 data bits, odd parity
Programming cable type
D2--DSCBL
Internal Field Supply Ratings
+24VDC , 0.5A maximum, isolated
Operating Temperature
32 to 140
F (0 to 60
_
C)
Storage Temperature
--4 to 158
F (--20 to 70
_
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
Terminal Type
Removable
Wire Gauge
One AWG14 or two AWG16, AWG24 minimum
Input Voltage Range for ON condition
80 -- 132 VAC, or 90 -- 150 VDC
Input Current
6 mA @ 132 VAC
6.8 mA @ 150 VDC
Maximum Voltage
132 VAC, or 150 VDC
ON Current/Voltage
>4 mA @ 80 VAC, or 90 VDC
OFF Current/Voltage
<2 mA @ 45 VAC, or 60 VDC
OFF to ON Response
< 8 mS
ON to OFF Response
<15 mS
Status Indicators
Logic Side
Commons
4 channels / common x 2 banks,
2 channels / common x 1 bank
Operating Voltage
12 -- 250 VAC, 12 -- 30 VDC @ 7A,
30 -- 150 VDC @ 0.5A, resistive
Output Current
7A / point (subject to derating)
14A / common
Maximum Motor Load
1/3 HP
Maximum Voltage
265 VAC, 150 VDC
Minimum Off Resistance
100 meg ohms @ 500 VDC
Smallest Recommended Load
10 mA
OFF to ON Response
15 mS
ON to OFF Response
5 mS
Status Indicators
Logic Side
Commons
2 channels / common x 4 banks
Fuses
None (external recommended)
Aux24V
Power Supply
F1--130AR
General
Specifications
AC Input
Specifications
X0 -- X7, X10 -- X11
Relay Output
Specifications
Y0 -- Y7
Summary of Contents for DL105
Page 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Page 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Page 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Page 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Page 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...