Electromechanical control unit
Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 2 to 500 (standard) or 2 to 5,000 (option)
Limit switching
Single switch (1 NC and 1 NO) for each end position, not galvanically isolated
Standard:
Tandem switch (2 NC and 2 NO) for each end position, switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switches (DUO limit switching), adjustable for each direction of op-
eration
Options:
Torque switching adjustable for directions OPEN and CLOSE
Torque switching
Single switch (1 NC and 1 NO) for each direction, not galvanically isolated
Standard:
Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated
Option:
Silver (Ag)
Standard:
Switch contact materials
Gold (Au), recommended for low voltage actuator controls
Option:
Potentiometer or 0/4 – 20 mA (electronic position transmitter)
Position feedback signal, analogue
(options)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Mechanical position indicator
Blinker transmitter (optional for modulating actuators)
Running indication
Self-regulating PTC heater, 5 – 20 W, 110 – 250 V AC/DC
Standard:
Heater in switch compartment
24 – 48 V AC/DC (for actuators with 3-phase AC/1-phase AC/DC motors)
or 380 – 400 V AC (for actuators with 3-phase AC motors)
Options:
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with AMExC or
ACExC actuator controls.
Service conditions
Indoor and outdoor use permissible
Use
Any position
Mounting position
≤
2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
–30 °C to +40/+60 °C
Standard:
Ambient temperature
–40 °C to +40 °C/+60 °C
–50 °C to +40 °C/+60 °C
–60 °C to +40 °C/+60 °C
Options:
For exact version, refer to actuator name plate.
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
IP68 with AUMA 3-phase AC motor
Standard:
Enclosure protection according to
EN 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Duration of continuous immersion in water: Max. 96 hours
●
Up to 10 operations during continuous immersion
For exact version, refer to actuator name plate.
Pollution degree 4 (when closed) according to EN 50178
Pollution degree
2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Valid for multi-turn actuators in version AUMA NORM (with AUMA plug/socket con-
nector, without actuator controls). Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:
Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Option:
KX-G: Same as KX, however aluminium-free version (outer parts)
Double layer powder coating
Coating
91
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
ACExC 01.2
Technical data