5.4.3.
KT/KM electrical connection
Figure 42: KT/KM electrical connection
[1]
Terminal carrier with screw-type/spring clamp terminals
[2]
Connection frame
Figure shows KT version
Short description
KT plug-in electrical connection with screw-type terminals for power connection and
spring clamp terminals for control contacts.
KM version with additional support terminals (terminal blocks) via terminal carrier.
Both versions (KT and KM) are available with terminal compartment in protection
type Ex e (increased safety) as well as in protection type Ex d (flameproof enclosure)
(refer to Ex marking on name plate).
Plug-in connection is made via the connection frame. For cable connection, simply
remove the cover. The connection frame with the cable entries remains within the
device. The flameproof interior of the connected devices remains sealed.
Technical data
Table 20:
KT/KM electrical connection
Control contacts
Power contacts
50
6 + PE conductors
1)
No. of contacts max.
1 to 36, 37 to 50
U1, V1, W1, U2, V2, W2,
Designations
12
3
Support terminals max.
250 V
1,000 V
Connection voltage max.
5 A
2)
25 A
Rated current max.
Spring clamp terminals
Screw connection
PE = Ring lug/U-bracket
Type of customer connection
2.5 mm
2
10 mm
2
Connection diameter max.
Four protective earth connections within frame
1)
The sum of the currents of all control contacts must not exceed 50 A.
2)
41
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
ACExC 01.2
Electrical connection