9.
Approach end position CLOSED anew and check minimum value (4.1 mA). If
necessary, correct the setting.
Information
If the maximum value cannot be reached, the selection of the reduction gearing must
be checked.
10.3.
Intermediate positions: set
Actuators equipped with DUO limit switching contain two intermediate position
switches. One intermediate position may be set for each running direction.
Figure 90: Setting elements for limit switching
Black section:
[1]
Setting spindle: Running direction CLOSE
[2]
Pointer: Running direction CLOSE
[3]
Mark: Intermediate position CLOSED is set
White section:
[4]
Setting spindle: Running direction OPEN
[5]
Pointer: Running direction OPEN
[6]
Mark: Intermediate position OPEN is set
Information
After 177 turns (control unit for 2 – 500 turns/stroke) or 1,769 turns (control unit for
2 – 5,000 turns/stroke), the intermediate switches release the contact.
10.3.1.
Running direction CLOSE (black section): set
1.
Move valve in direction CLOSE to desired intermediate position.
2.
If you override the tripping point inadvertently: Turn valve into the opposite dir-
ection and approach intermediate position again in direction CLOSE.
Information: Always approach the intermediate position in the same direction
as in later electrical operation.
3.
Press down and turn setting spindle [1] with screw driver in direction of the
arrow and observe the pointer [2]: While a ratchet click is felt and heard, the
pointer [2] moves 90° every time.
4.
As soon as the pointer [2] is 90° from mark [3]: Continue turning slowly.
5.
As soon as the pointer [2] moves to mark [3]: Stop turning and release setting
spindle.
➥
The intermediate position setting in running direction CLOSE is complete.
6.
If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
10.3.2.
Running direction OPEN (white section): set
1.
Move valve in direction OPEN to desired intermediate position.
74
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
Commissioning (optional equipment settings)
ACExC 01.2