F4
Table 35:
Secondary fuse F4 (internal AC supply)
1)
AUMA art. no.
F4
G-fuse according to IEC 60127-2/III
5 x 20 mm
Size
K001.184
1.25 A T; 250 V
Voltage output (power supply unit) = 24 V
—
—
Voltage output (power supply unit) = 115 V
Fuse for: Switch compartment heater, reversing contactor control, PTC tripping device (at 24 V AC
only), at 115 V AC also control inputs OPEN, STOP, CLOSE
1)
F5
Automatic reset fuse as short-circuit protection for external 24 V DC supply for
customer (see wiring diagram)
11.3.2.
Fuse replacement
11.3.2.1. Replace fuses F1/F2
Information: Only valid for version with electrical connection of KES or KT type
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Disconnect device from the mains before opening.
1.
Remove electrical connection from actuator controls.
Figure 91:
2.
Pull fuse holder out of pin carrier, open fuse cover and replace old fuses by
new ones.
81
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
ACExC 01.2
Corrective action