9.
Commissioning (basic settings)
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Observe heat-up time for ambient temperatures below –30 °C.
3.
Perform basic settings.
9.1.
Heat-up time for low temperature version
Please note that for low temperature versions, the controls require a heat-up time.
This heat-up time applies if both actuators and actuator controls are not live and
temperature falls below the permissible operation and storage temperature of –30 °C.
Under these conditions and after connection to the voltage supply, the following
heat-up times must be complied with prior to commissioning:
For –30 °C = 5 min.
For –40 °C = 40 min.
For –60 °C = 80 min.
9.2.
Type of seating: set
Valve damage due to incorrect setting!
→
The type of seating setting (limit or torque seating) must match the selection for
the valve.
→
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value:
Limit
Setting values:
Limit
Seating in end positions via limit switching.
Torque
Seating in end positions via torque switching.
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: Press and enter ID
M0086
or
M0087
➥
Display indicates:
End position CLOSED
65
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
ACExC 01.2
Commissioning (basic settings)