Technical data
Table 16:
KP/KPH electrical connection
Control contacts
Power contacts
38 pins/s protective earth con-
ductor (PE)
3 + protective earth conduct-
or (PE)
No. of contacts max.
1 to 24, 31 to 40, 47 to 50, PE
U1, V1, W1,
(PE)
Designations
250 V
525 V
Connection voltage max.
10 A
25 A
Rated current max.
Screw connection
Screw connection
Type of customer connection
1.5 mm
2
6 mm
2
Connection diameter max.
5.4.1.1. Terminal compartment: open
Figure 33: Open terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Flameproof frame
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
Information: The terminal compartment is designed in protection type Ex e
(increased safety). The flameproof interior of the connected device remains
closed when removing the cover [1].