Table 24:
User levels and authorisations
Authorisation/password
Designation (user level)
Verify settings
No password required
Observer (1)
Change settings
Default factory password: 0000
Operator (2)
Reserved for future extensions
Maintenance (3)
Change device configuration
e.g. type of seating, assignment of output contacts
Default factory password: 0000
Specialist (4)
Service staff
Change configuration settings
Service (5)
AUMA administrator
AUMA (6)
6.4.1.
Password entry
1.
Select desired menu and hold down push button for approx. 3 seconds.
➥
Display indicates the set user level, e.g
Observer (1)
2.
Select higher user level via
Up ▲
and confirm with
Ok
.
➥
Display indicates:
Password 0***
3.
Use push buttons
Up ▲ Down ▼
to select figures 0 to 9.
4.
Confirm first digit of password via push button
Ok
.
5.
Repeat steps 1 and 2 for all further digits.
➥
Having confirmed the last digit with
Ok
, access to all parameters within one
user level is possible if the password entry is correct.
6.4.2.
Password change
Only the passwords of same or lower access level may be changed.
Example: If the user is signed in as
Specialist (4)
, he/she can change passwords as
for password levels (1) through (4).
Device configuration M0053
Service functions M0222
Change passwords M0229
Menu item
Service functions M0222
is only visible, if user level
Specialist (4)
or higher
is selected.
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
53
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
ACExC 01.2
Operation