EMS Alarm Guide
42
Document #: 94602
EMS
Table 3-4: Configuration Error
Description
Configuration Error
SNMP Alarm
acBoardConfigurationError
SNMP OID
1.3.6.1.4.1.5003.9.10.1.21.2.0.2
Alarm Title
Configuration Error
Alarm Type
Equipment Alarm
Alarm Source
Probable Cause
Underlying resource unavailable
Severity
Critical
Additional Info
NULL
Corrective Action
Inspect the run-time specific string to determine the nature of the
configuration error. Fix the configuration error using the appropriate tool:
Web interface, EMS, or
ini
file. Save the configuration and if necessary
reset the device.
3.2.3 Temperature
Alarm
The table describes the alarm and shows the alarm information presented to Users. For
Users' convenience, all alarms generated by the device have the same standard structure,
including the fields shown in the table.
Table 3-5: Temperature Alarm
Description
The temperature alarm is set off when the temperature exceeds 60
degrees Celsius, and ceases when the temperature again falls below
55 degrees Celsius.
Alarm raise - 'The temperature is too high'
Alarm clear - 'The temperature is normal'
SNMP Alarm
acBoardTemperatureAlarm
SNMP OID
1.3.6.1.4.1.5003.9.10.1.21.2.0.3
Alarm Title
Temperature Alarm
Alarm Type
Equipment Alarm
Alarm Source
Probable Cause
Temperature unacceptable
Severity
Critical
Additional Info
NULL
Corrective Action
Inspect the system. Determine if all fans in the system are operating
correctly.