PROGRAMMABLE PARAMETERS
88
EMX4i User Manual 710-14888-00C
7H –
Input B Initial Delay
Range:
00:00 - 30:00 (minutes:seconds) Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is
counted from the time a start signal is received. The state of the
input is ignored until the initial delay has elapsed.
7I –
Reset/Enable Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the reset input (10, 11) is normally open or
normally closed.
NOTE
If the reset input is active, the starter will not operate.
7J –
Input A Name
Options:
Input A Trip (default)
Controller
Low Pressure
PLC
High Pressure
Vibration Alarm
Pump Fault
Field Trip
Low Level
Interlock Trip
High Level
Motor Temperature
No Flow
Motor Protection
Starter Disable
Feeder Protection
Custom Message
Description:
Selects a message for the keypad to display when Input A is active.
The custom message can be loaded via the USB port. Refer to
USB Save & Load
on page 36 for details.
7K –
Input B Name
Options:
Input B Trip (default)
Controller
Low Pressure
PLC
High Pressure
Vibration Alarm
Pump Fault
Field Trip
Low Level
Interlock Trip
High Level
Motor Temperature
No Flow
Motor Protection
Starter Disable
Feeder Protection
Custom Message
Description:
Selects a message for the keypad to display when Input B is active.