APPLICATION EXAMPLES
710-14888-00C EMX4i User Manual
109
1
Digital inputs
K1
Main contactor
A Manual start
10, 11 Reset input
B Manual stop
11, 12 Start/stop input
C Automatic operation
(scheduled start/stop)
13, 14 Programmable input A
(set = Command Override: Digital)
2
Control voltage
33, 34 Main contactor output
3
Three-phase supply
R1, R2, R3 Motor temperature protection
4
Smart card
B33, B34 Flow protection
5
Remote keypad
(optional)
B23, B24 Pressure protection
6
Pressure sensor
B13, B14 Depth protection
7
Flow sensor
8
Depth sensor
9
Temperature sensor
Parameter settings:
•
Parameter 1A
Command Source
: select 'Smart Card + Clock'.
•
Parameters 4A~4X Auto-Start/Stop: Set as required.
•
Parameter 7A
Input A Function
: select 'Command Override: Digital'.
•
Parameters 30A~30O Pump Input Configuration: Set as required.
•
Parameters 31A~31D Flow Protection: Set as required.
•
Parameters 32A~32F Pressure Protection: Set as required.
•
Parameters 34A~34D Depth Protection: Set as required.
•
Parameters 35A~35B Thermal Protection: Set as required.