PROGRAMMABLE PARAMETERS
64
EMX4i User Manual 710-14888-00C
Parameter Group
Default Setting
4R
Thursday Stop Time
00:00 (hh:mm)
4S
Friday Mode
Start/Stop Disable
4T
Friday Start Time
00:00 (hh:mm)
4U
Friday Stop Time
00:00 (hh:mm)
4V
Saturday Mode
Start/Stop Disable
4W
Saturday Start Time
00:00 (hh:mm)
4X
Saturday Stop Time
00:00 (hh:mm)
5
Protection Levels
5A
Current Imbalance
30%
5B
Current Imbalance Delay
00:03 (mm:ss)
5C
Undercurrent
20%
5D
Undercurrent Delay
00:05 (mm:ss)
5E
Overcurrent
400%
5F
Overcurrent Delay
00:00 (mm:ss)
5G
Undervoltage
350 V
5H
Undervoltage Delay
00:01 (mm:ss)
5I
Overvoltage
500 V
5J
Overvoltage Delay
00:01 (mm:ss)
5K
Underpower
10%
5L
Underpower Delay
00:01 (mm:ss)
5M
Overpower
150%
5N
Overpower Delay
00:01 (mm:ss)
5O
Excess Start Time
00:20 (mm:ss)
5P
Restart Delay
00:10 (mm:ss)
5Q
Starts per Hour
0
5R
Phase Sequence
Any Sequence
6
Protection Actions
6A
Auto-Reset Count
0
6B
Auto-Reset Delay
00:05 (mm:ss)
6C
Current Imbalance
Soft Trip and Log
6D
Undercurrent
Soft Trip and Log
6E
Overcurrent
Soft Trip and Log
6F
Undervoltage
Soft Trip and Log
6G
Overvoltage
Soft Trip and Log