SYSTEM DESIGN
710-14888-00C EMX4i User Manual
17
CAUTION
DC Brake: A high brake torque setting can result in peak currents up to
motor DOL being drawn while the motor is stopping. Ensure protection
fuses installed in the motor branch circuit are selected appropriately.
CAUTION
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with
the National Electrical Code and any additional local codes.
3.12
IEC Coordination with Short Circuit Protection Devices
These fuses were selected based on start current of 300% FLC for 10 seconds.
Nominal Rating
(A)
SCR I
2
t (A
2
s)
Type 1
coordination
480 VAC, 65 kA
Bussmann NH
fuse links
Type 2
coordination
690 VAC, 65 kA
Bussmann
DIN 43 653
EMX4i-0024B
24
1150
40NHG000B
170M3010
EMX4i-0042B
42
7200
63NHG000B
170M3013
EMX4i-0052B
52
80NHG000B
EMX4i-0064B
64
15000
100NHG000B
170M3014
EMX4i-0069B
69
EMX4i-0105B
105
80000
170M3015
EMX4i-0115B
115
160NHG00B
EMX4i-0135B
135
125000
170M3016
EMX4i-0184B
184
250NHG2B
EMX4i-0200B
200
320000
170M3020
EMX4i-0229B
229
315NHG2B
EMX4i-0250B
250
170M3021
EMX4i-0352B
352
202000
355NHG2B
170M6009
EMX4i-0397B
397
400NHG2B
EMX4i-0410B
410
320000
425NHG2B
170M6010
EMX4i-0550B
550
781000
630NHG3B
170M6012
EMX4i-0580B
580