PROGRAMMABLE PARAMETERS
70
EMX4i User Manual 710-14888-00C
9.5
1 Motor Details
1A –
Command Source
Options:
Digital Input
(default)
The EMX4i will accept start and stop
commands from the digital inputs.
Network
The EMX4i will accept start and stop
commands from the communication
expansion card.
Remote Keypad The EMX4i will accept start and stop
commands from the Remote Keypad.
Clock
The EMX4i will start and stop as scheduled in
parameters 4D to 4X.
Smart Card
The EMX4i will accept start and stop
commands from the smart card.
Smart Card +
Clock
The EMX4i will accept start commands from
the smart card if they are within the operating
schedule set in parameters 4A to 4X. A stop
command from the smart card will be
accepted regardless of the schedule.
Timer
After a start signal is received, the EMX4i will
start and stop the motor according to the
timers set in parameters 4B and 4C.
Description:
Selects the command source for controlling the soft starter.
1B –
Motor Full Load Current
Range:
Model dependent
Description:
Matches the starter to the connected motor's full load current.
Set to the full load current (FLC) rating shown on the motor
nameplate.
1C –
Motor kW
Range:
0 - 9999 kW
Default:
0
Description:
Sets the running power of the connected motor, in kilowatts.
This setting is the basis for power reporting and protection.
NOTE
The motor nameplate may state different power ratings for different supply
voltages or power connections. Ensure that the motor kW setting is
accurate for the installation.