PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual
85
Description:
Selects the soft starter's response to the protection event. If set
to Stop, the EMX4i will perform a soft stop, then can be restarted
without a reset.
6N –
Remote Keypad Fault
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6O –
Frequency
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6P –
Phase Sequence
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6Q –
Motor Overtemperature
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6R –
Motor Thermistor Circuit
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6S –
Shorted SCR Action
Options:
3-Phase Control Only (default)
PowerThrough
Description:
Selects whether the soft starter will allow PowerThrough
operation, if the soft starter is damaged on one phase. The soft
starter will use two-phase control, allowing the motor to
continue operating in critical applications. Refer to
PowerThrough
on page 47 for further information.