TROUBLESHOOTING
710-14888-00C EMX4i User Manual
115
Display
Possible cause/Suggested solution
Instantaneous
overcurrent
This trip is not adjustable.
The current on all three phases has exceeded 7.2 times the value
of parameter 1B
Motor Full Load Current
.
Causes can include a locked rotor condition or an electrical fault
in the motor or cabling.
Related parameters: None
Internal fault x
Where 'X' is a number.
This trip is not adjustable.
The EMX4i has tripped on an internal fault. Contact your local
supplier with the fault code (X).
Internal fault 88
The soft starter firmware does not match the hardware.
Keypad disconnected
Parameter 1A
Command Source
is set to Remote Keypad but the
EMX4i cannot detect a remote keypad.
If a remote keypad is installed, check the cable is firmly
connected to the soft starter.
If no remote keypad is installed, change the setting of parameter
1A.
Related parameters: 1A
L1 phase loss
L2 phase loss
L3 phase loss
This trip is not adjustable.
During pre-start checks the starter has detected a phase loss as
indicated.
In run state, the starter has detected that the current on the
affected phase has dropped below 10% of the programmed
motor FLC for more than 1 second, indicating that either the
incoming phase or connection to the motor has been lost.
Check the supply and the input and output connections at the
starter and at the motor end.
Related parameters: None
L1-T1 shorted
L2-T2 shorted
L3-T3 shorted
During pre-start checks the starter has detected a shorted SCR
or a short within the bypass contactor as indicated. Consider
using PowerThrough to allow operation until the starter can be
repaired.
Related parameters: 6S