PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual
75
3E –
Initial Current-2
Range:
100% - 600% FLC
Default:
200%
Description:
Sets the initial start current level for current ramp starting, as a
percentage of motor full load current. Set so that the motor
begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current
equal to the current limit.
3F –
Current Limit-2
Range:
100% - 600% FLC
Default:
350%
Description:
Sets the current limit for constant current and current ramp
soft starting, as a percentage of motor full load current.
NOTE
The EMX4i will apply the current limit on all soft starts, including adaptive
control. lf the current limit is too low or the start ramp time (parameter 2B)
is too short, the motor may not start successfully.
3G –
Adaptive Start Profile-2
Options:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Description:
Selects which profile the EMX4i will use for an Adaptive Control
soft start.
3H –
Kickstart Time-2
Range:
0 – 2000 milliseconds
Default:
0000 milliseconds
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
3I –
Kickstart Level-2
Range:
100% - 700% FLC
Default:
500%
Description:
Sets the level of the kickstart current.
3J –
Jog Torque-2
Range:
20% - 100%
Default:
50%
Description:
Sets the current limit for jog operation.
3K –
Stop Mode-2
Options:
Coast To Stop
DC Brake
TVR Soft Stop (default)
Soft Brake
Adaptive Control
Description:
Selects the stop mode.