www.atestgaz.pl
Product code
Current consumed [mA]
PW-044
PW-017
SM
SP
TS
0
HL
20
LCD
35
FLED
FLED.A
75
EL
ELm
VOC
DET
0
70
LCD
80
FLED
FLED.A
125
IR
0
HL
55
HH
95
LCD
HL
65
HH
105
FLED
FLED.A
HL
110
HH
150
PID
0
HH
75
LCD
90
FLED
FLED.A
130
PW-093
SR
TS
0
HR
20
FLED
75
Table 14: Current consump!on by connected detectors
Informa on on the types of cables required and the method for preparing the gas detec on system
connec ons – see appendix [3].
Once the system is installed perform a load test – see sec on 8.4
.
Examples of correct and incorrect device selec on are presented below:
Example 1:
Power supply
230 V AC
10 x detector PW-017-SP-TS-LCD-ABS-0,
current input 10 x 35 mA = 350 mA
6 x detector PW-044-SM-EL-0-ALB-T,
current input 6 x 70 mA = 420 mA
1 x visual-acous c indicator,
current input 1 x 250 mA = 250 mA
Current input for indicators:
250 mA < 1150 mA
Correctly
Total current input:
1020 mA < 1500 mA
Correctly
system configured
correctly
p. 32|37
User's Manual: POD-026-ENG R11