Example 2:
Power supply 230 V AC
10 x detector PW-044-SM-ELm-0-ALB-0,
current input 10 x 70 mA = 700 mA
2 x visual-acous c indicator,
current input 2 x 480 mA = 960 mA
Current input for indicators:
960 mA < 1150 mA
Correctly
Total current input:
1660 mA > 1500 mA
Incorrectly
system configured
incorrectly
Example 3:
Power supply 24 V DC
5 x detector PW-044-SM-ELm-0-ALB-0,
current input 5 x 70 mA = 350 mA
2 x visual-acous c indicator,
current input 2 x 600 mA = 1200 mA
Current input for indicators:
1200 mA > 1150 mA
Incorrectly
Total current input:
1550 mA < 2500 mA
Correctly
system configured
incorrectly
8
Life cycle
8.1
Transport
The unit should be transported the same way as a new one. If its original packaging, protec ve extrusion or
other protec ve components are unavailable, protect the unit against mechanical shocks, vibra ons and
moisture with other equally effec ve methods.
8.2
Installa!on
Install the unit on a flat, ver cal wall as shown in Figure 1. Use the drill template provided in the package for
drilling holes. If stranded cables are used to connect the unit, use bushing terminals to the ends of these
cables.
It is unacceptable to combine in one connector two wires which are not pinched in one cable
lug.
Do not place the cable reserve in the device. Bare wires or wires surplus may create a danger
of electric shock or equipment damage.
Do not leave disconnected cables inside the device.
Incorrect cable rou ng can lead to reducing the device's immunity from electromagne c
interference.
p. 33|37
User's Manual: POD-026-ENG R11