www.atestgaz.pl
5.6
Detailed detector view
The screen is divided into a few sec ons (see figure 18).
Detector panel – see sec on 5.5.
Detector No. – detector system number.
Detector loca on – informa on on physical detector loca on.
Detector indica on – current value measured by the detector.
Detector status
This sec on presents a text descrip on of the detector status. Possible messages include:
Message
Descrip!on
<no message>
The detector operates correctly, measures gas concentra on, no exceeding or special
situa ons.
WARNING 1
WARNING 2
ALARM
Detector indica on above warning 1,
warning 2,
or alarm threshold.
FAULT :<fault code>
The detector fault, it does not measure. Fault code – see gas detector manual. Text message
explaining fault code – see detector's menu – see sec on 5.8.
NC.FAULT: <fault code> Detector malfunc on measurement accuracy loss. Fault code – see gas detector manual.
Text message explaining fault code – see detector's menu – see sec on 5.8.
OVERLOAD
Gas concentra on is above the overload value.
SENSOR LOCKED
The detector is in locked mode – last measured value has been latched. It does not measure.
CALIBRATION
The detector is in calibra on mode – its indica ons are ignored.
TEST
The detector is in test mode – its indica ons are simulated, but all outputs are treated as
real. Possible gas alarms or faults.
WARMING UP...
Preparing detector for opera on. Its indica ons are ignored.
INHIBIT MODE
The detector has been temporarily excluded from the system. In this status detector related
flags are ignored (see NOTES Table 12).
p. 22|37
User's Manual: POD-026-ENG R11
Figure 18: Screen showing detailed detector view
on
func ons
Detector
status
Detector panel
Detector No.
Loca on
Detector indica on