Bit
Flag
Description
5
-
Unused – always zero
6
Gas_HiHi_Range
Gas overload
7
Sensor_Lock
Sensor lock (last measurement latched)
8
Calibration
Calibration mode
9
Test
Test mode
10
Warm_Up
Sensor warming up
11
Sensor_Inhibit
Inhibit mode
12
Comm_Error
Detector communication error
13
Calibration_Warning Calibration time out (non-critical failure)
14
Measure
Detector takes measurements
15
System_Stop
System stopped
N – gas concentration. Value 0 correspond to 0 concentration, value 1000 corresponds to detector
maximum range.
6.1.2
PK1 – PK8 output status and DI1 – DI2 input status (read only)
Register
Name
Description
Type / range
40065
DO_Status
Control Unit output status. Specific bit description
bit 0 – status PK1
bit 1 – status PK2
bit 2 – status PK3
bit 3 – visual indicator output
bit 3 – acoustic indicator output
bit 4 – PK failure
bit 5 – 15 – unused (can adopt any values)
value 0 – inactive output
value 1 – active output
flags
40066
DI_Status
Control Unit input status. Specific bit description
bit 0 – DI status
bit 1 – 15 – unused (can adopt any values)
value 0 – inactive input
value 1 – active input
flags
6.1.3
Control Unit status (read only)
Register
Name
Description
Type / range
40067
CU_Status
Control Unit module status
flags
CU_Status – Control Unit module status. For specific bit description see the Table below.
Bit
Flag
Description
0
System_fail
Collective system failure
1
CU_fail
Control Unit module failure
2..15
-
Unused – always zero
Atest Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
Appendix: PU-Z-062-ENG R04
s. 5|8
•
Summary of Contents for Sigma Control L
Page 1: ...POD 026 ENG R11 User s Manual Control Unit Sigma Control L Product code PW 072 A...
Page 29: ...www atestgaz pl p 29 37 User s Manual POD 026 ENG R11...
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......