www.atestgaz.pl
6.1.4
Detector Measurement Head temperature (read only)
No.
Register
Name
Description
Type
1
40068
Temp.
Temperature in the detector’s measurement head [°C]
S16
2
40069
Temp.
Temperature in the detector’s measurement head [°C]
S16
...
...
...
...
...
20
40087
Temp.
Temperature in the detector’s measurement head [°C]
S16
6.1.5
External Digital Inputs (read / write)
Register
Name
Description
Type / range
44001
Static_External_DI
External DI – static
Write 1 – sets input as active
Write 0 – sets input as inactive
Read – current input state
Application: source for output activation
flags
44002
Pulse_External_DI
External DI – pulse
Write 1 – Previous value 0: generates a single positive impulse
at a selected output
Write 1 – Previous value 1: no changes
Write 0 – input with no changes (Previous input value remains)
Read – always 0
Application: temporary deactivation, latch resetting
flags
Static_External_DI, Pulse_External_DI – for bits description see the table below.
Bit
Flag
Description
Default configuration
0
External_DI_0
Input no. 0
Temporary internal buzzer deactivation
1
External_DI_1
Input no. 1
Temporary external acoustic indicator deactivation
2
External_DI_2
Input no. 2
Temporary internal buzzer activation
3
External_DI_3
Input no. 3
Visual alarm indicator cancellation, backed up
4
External_DI_4
Input no. 4
Visual indicator activation
5
External_DI_5
Input no. 5
R1 relay activation
6
External_DI_6
Input no. 6
R2 relay activation
7
External_DI_7
Input no. 7
R3 relay activation
8
External_DI_8
Input no. 8
FAULT relay activation
9..15
External_DI_9..15 Input no. 9..15
Unassigned
2
S16 – 16-bit unsigned.
Atest Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
Appendix: PU-Z-062-ENG R06
p. 6|8
•