To configure transmission parameters use an appropriate option in the control unit menu, where the
module is installed (see user’s manual). The module offers the following settings:
protocol:
Modbus ASCII / Modbus RTU
network address:
1 – 255
baud rate:
4800, 9600, 19200, 38400, 57600, 15200 bod
parity control:
parity (E), odd (O), no (N)
number of character bits:
7 (only for Modbus ASCII) or 8
6
Memory maps
6.1
Memory map for Sigma Control L Unit
Register range
Description
40001 – 40040
Detector status at channels 1 – 20
40041 – 40064
Unused – always zero
40065 – 40066
Input and output status
40067 – 40067
Control Unit status
40068 – 40087
Temperature in detector’s measuring head at channels 1 – 20
40088 – 40099
Unused – always zero
43501 – 43503
Interface for operator’s command execution
44001 – 44002
External DI (Digital Inputs)
6.1.1
Detectors statuses
Channel No. Register
Name
Description
Type
1
40001
State_A
Detector status
flags
40002
N
Output (concentration)
U16
2
40003
State_A
Detector status
flags
40004
N
Output (concentration)
U16
...
...
...
...
...
20
40039
State_A
Detector status
flags
40040
N
Output (concentration)
U16
State_A –detector status at specific channel. For bits description see table below
Bit
Flag
Description
0
Collective_W1
Warning 1 threshold exceeded
1
Collective_W2
Warning 2 threshold exceeded
2
Collective_AL
Alarm threshold exceeded
3
Collective_CrFail
Collective critical failure information
4
Collective_NonCrFail Collective non-critical failure information
5
-
Unused – always zero
1
U16 – 16-bit unsigned.