Life cycle
8.1
Transport
The unit should be transported the same way as a new one. If its original packaging, protective extrusion or
other protective components are unavailable, protect the unit against mechanical shocks, vibrations and
moisture with other equally effective methods.
8.2
Installation
Install the unit on a flat, vertical wall as shown in Figure 1. The unit must be accessible to system operators
but, if possible, prevented from access of unauthorized persons. Elevation of the installation place must be
convenient for operation and maintenance.
Use the drill template provided in the package for drilling holes. If stranded cables are used to connect the
unit, use bushing terminals to the ends of these cables.
It is unacceptable to combine in one connector two wires which are not pinched in one cable
lug.
Do not place the cable reserve in the device. Bare wires or wires surplus may create a danger
of electric shock or equipment damage.
Do not leave disconnected cables inside the device.
Incorrect cable routing can lead to reducing the device's immunity from electromagnetic
interference.
Unused screw terminals must be tightened.
p. 34|38
User's Manual: POD-026-ENG R17