www.atestgaz.pl
Bit
Flag
Description
Default configuration
0
External_DI_0
Input no. 0
Temporary internal buzzer deactivation
1
External_DI_1
Input no. 1
Temporary external acoustic indicator deactivation
2
External_DI_2
Input no. 2
Temporary internal buzzer activation
3
External_DI_3
Input no. 3
Visual alarm indicator cancellation, latched
4
External_DI_4
Input no. 4
Visual indicator activation
5
External_DI_5
Input no. 5
R1 relay activation
6
External_DI_6
Input no. 6
R2 relay activation
7
External_DI_7
Input no. 7
R3 relay activation
8
External_DI_8
Input no. 8
FAULT relay activation
9..15
External_DI_9..15 Input no. 9..15
Unassigned
7.1.6
Interface for executing operator commands (read / write)
Register
Name
Description
Type / range
43501
Command_Status
Current command execution status
Write – data ignored
Read – status, possible values include:
• 0 – inactive
• 1 – command in progress
• 2 – task completed successfully; this value is latched up for 5 s
from execution
• 3 – command execution not succeeded, incorrect command or
its parameters; this value is latched for 5 s from execution
U16
43502
Command_Code
Command code to be executed
Write – command code to be executed; Writing to this log initiates
command execution
Read – current command code value
For possible values – see description below
U16
43503
Command_Param
Command parameter
Read, Write – Command parameter
For possible values – see description below
U16
List of commands:
Command code
Description
1
Disable detector lock
Execution parameters – detector channel number to unlock, possible values: 1 – 20