Bit
Flag
Description
6
Gas_HiHi_Range
Gas overload
7
Sensor_Lock
Sensor lock (last measurement latched)
8
Calibration
Calibration mode
9
Test
Test mode
10
Warm_Up
Sensor warming up
11
Sensor_Inhibit
Inhibit mode
12
Comm_Error
Detector communication error
13
Calibration_Warning Calibration time out (non-critical failure)
14
Measure
Detector takes measurements
15
System_Stop
System stopped
N – gas concentration. Value 0 correspond to 0 concentration, value 1000 corresponds to detector
maximum range.
6.1.2
Output status and DI1 – DI2 input status (read only)
Register
Name
Description
Type / range
40065
DO_Status
Control Unit output status. Specific bit description
bit 0 – state of R1 relay
bit 1 – state of R2 relay
bit 2 – state of R3 relay
bit 3 – visual indicator output
bit 3 – acoustic indicator output
bit 4 – FAULT relay
bit 5 – 15 – unused (can show any values)
value 0 – inactive output
value 1 – active output
flags
40066
DI_Status
Control Unit input status. Specific bit description
bit 0 – DI status
bit 1 – 15 – unused (can show any values)
value 0 – inactive input
value 1 – active input
flags
6.1.3
Control Unit status (read only)
Register
Name
Description
Type / range
40067
CU_Status
Control Unit module status
flags
CU_Status – Control Unit module status. For specific bits description see the table below.
Bit
Flag
Description
0
System_fail
Collective system failure
1
CU_fail
Control Unit module failure
2..15
-
Unused – always zero