www.atestgaz.pl
10
Technical specifications
Rated power supply parameters
• V
CC
; Power consumption
230 V ~ ± 10%; 60 W
21 – 29 V ; 60 W
Environment (operation and storage)
• Ambient temperature range
• Relative humidity range
• For power supply 230 V ~: -10 – +40°C
• For power supply 24 V : -10 – +50°C
When an extension module is used, the
temperature range may be limited – details see
appendices [2] and [3].
10 – 90% long term, 0 – 99% short term, without condensation
IP
IP 65
Output capacity
• For power supply 230 V ~: 1.5 A
• For power 24 V : 2.3 A
For signaller output, independent of the power, max 1.15 A
More information in section 7
Digital input parameters
• R
in
• Inactive
• Active
• Time parameters
10 kΩ
0 – 1 V any polarization
10 – 30 V any polarization
The shortest pulse duration noticeable by the system is 0.2 s
Digital output parameters
• Relays
• Indicator outputs
3 pieces, current carrying capacity:
DC1
: 230 V / 0.25 A
DC1: 24 V / 3 A
AC1: 230 V ~ / 3 A
Total current for all contacts not to exceed 3 A
Active
, 24 V / 1.15 A, fused
Digital communication parameters
• Port “DETECTORS BUS”
• Electric standard
• Communication protocol
• Service port
• Electric standard
• Connector type
RS-485 non-isolated
Sigma BUS
USB non-isolate, class V2.0
Mini-B
Integrated signalling equipment (visual)
LCD display, monochromatic, approx. 2.4”
LED indicator
Integrated signalling equipment (audible)
60 dB from 1 m
Protection class
I – for 230 V ~ power supply, III – for 24 V power supply
Unit design according to class II
6
Provided power value is a power available for the whole system – i.e. for Control Unit, Detectors, Indicators and other components. The Sigma
Control L alone consumes 10 W.
7
EN 60947 – Low-voltage switchgear and control gear.
8
If to “24 VDC” input a voltage of approx. 21 – 29 V is connected, then the output voltage is the same as the Sigma Control L Unit power supply
voltage.
p. 37|38
User's Manual: POD-026-ENG R17