Additional Features
16
Operating Instructions (continued)
Voice Module Activation Output - Optional
1. This output is active during the timing out (Red and Green LED flashing) of the
Delayed Egress Alarm and continues until unit is unlocked
2. Output is Form C relay contacts, (SPDT) rated 1 amp @ 24VDC
Gang Mode for Banks of Doors - Optional
1. When Electroguards are connected on a bank of doors, it is possible to have them all released simultaneously
(Layout
below)
2. All ganged units
must
share the same power supply to avoid ground loops
3. All interconnecting equipment
must
be located within the same area
4. A total of 12 doors can be ganged together when randomly distributed across 1000 feet of cable or less using
18 gauge wire
BC-Prefix Option
The BC prefix for Electroguard™ indicates that the unit has been programmed to comply with the section of the BOCA code relating
to delayed egress.
BOCA allows for automatic reset of the delayed egress unit. Under BOCA, the unit can automatically reset thirty (30) seconds after
the door has been cycled. If the door is opened any time during the thirty (30) seconds, the timer in the unit resets and waits another
thirty (30) seconds before rearming. This requires a door position switch (3287).
Note: If a door position switch is not used (Blue wire connected to Black wire), the unit will automatically reset in 30
seconds.
See
Note
4
Page 27 Art
Door
#1
Door
#2
Door
#3
Red/Green
Red/Green
Red/Green
Red/Yellow
Red/Yellow
Red/Yellow
Latchbolt Monitor
- indicates to the circuitry that the latchbolt is
being retracted while the unit is armed. If the latchbolt is depressed
for 10 seconds or longer while the unit is armed, an irreversible
alarm condition is triggered. The unit will start the 15 second delay to
egress. At this point, the rail assembly will release allowing egress.
8500 Main Chassis Dwg