System Wiring Examples
14
Pigtail harness
assembly with
8-pin connector
NOTE: This drawing shows
the BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED
110-120 VAC
2.5 AMP polyswitch breaker
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
GN
D
NEUT
HOT
Black
Unconnected
terminal for
switch hookup
(- 24), 1
1
7 5
6 4
3
2
8
Green (EG), 4
Normally Closed Fire
Alarm Contact
(If Required)
Red
Red
(+24), 2
Blue (DS), 6
White (FA), 3
1
2
3
AC
F
AC
Battery Pack
Black
Output
From transformer
Connector
to power on LED
Low voltage AC
DC
DC
Voltage adjust for
battery backup
Line voltage
fuse (1 AMP)
Sample Wiring #1 – Basic 59- Delayed Egress with Fire Alarm
During a fire alarm condition, the fire alarm contact opens which de-energizes the rail magnet and allows immediate egress
Plug pigtail harness
connector into
8-pin hinge connector
at frame side of door
Electric hinge with
8-pin connectors
Raceway harness with 8 & 4-pin
connectors. The 4-pin connector
is not used here
59- 80 Series Rail with 8 &
4-pin connectors The 4-pin
connector is not used here
Note: Typical raceway location is
shown. Other locations may exist
depending on door type
Wiring Notes:
1. Rail, raceway, electric hinge and
pigtail 8-pin connector terminations
and wire colors all match
2. Tape or cap off ends of unused pigtail
wires (not shown) to ensure that they
don’t short
3. A fire alarm tie-in is required on fire
rated openings. If fire alarm is not
required, connect the white wire to
the black (- 24VDC) wire
4. The fire alarm contact could be
wired to drop 24VDC power to rail.
In this case, terminate fire alarm
contact between the red (+ 24VDC)
wire and 24VDC output.
Connect the white (FA) wire to the
black (- 24VDC) wire