System Wiring Examples (continued)
Pigtail harness
assembly with
8-pin connector
Normally Closed Fire
Alarm Contact
(If Required)
Black
(
-
24),
1
Red
(+24),
2
6, Blue (DS)
White (FA), 3
1
7 5
6 4
3
2
8
Green (EG), 4
C
8
7
4 5
1 2 3
9
6
* 0 #
5, Orange (EI)
(
-
)
NO
(+)
4291
Keypad
(inside)
8, Yellow (RAR - NO)
Brown (RAR - C), 7
Green (NC)
3287
Door status
switch
(-)
4380H
(remote)
horn
(+)
White (C)
RAR contact shown in
rail powered on state
When door is closed,
the green wire is
shorted to white wire
NOTE: This drawing shows
the BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED
110-120 VAC
2.5 AMP polyswitch breaker
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
GND
NEUT
HOT
Unconnected
terminal for
switch hookup
Red
1
2
3
AC
F
AC
Battery pack
Black
Output
From transformer
Connector
to power on LED
Low voltage AC
DC
DC
Voltage adjust for
battery backup
Line voltage
fuse (1 AMP)
Sample Wiring #2 – 59- Electroguard™ Exit Device with inside Keypad,
Fire Alarm, Door Status and Remote Horn
A valid code entry at the 4291 (Inside) keypad shunts the Electroguard™ exit device and allows egress for a time period
programmable at the keypad. During a fire alarm condition, the contact opens which de-energizes the rail electromagnet and allows
immediate egress. When the rail is armed and the door is forced open, the 3287 door status switch signals the rail sounding the rail
alarm. When the rail is armed and violated, the remote alarm relay sends 24VDC to the 4380H remote horn.
Plug pigtail harness
connector into
8-pin hinge connector
at frame side of door
Electric hinge with
8-pin connectors
Raceway harness with 8 & 4-pin
connectors. The 4-pin connectors
are not used here
59- 80 Series Rail with
8 & 4-pin connector. The
4-pin connector is not
used here
Note: Typical raceway location is
shown. Other locations may exist
depending on door type
Wiring Notes:
1. Rail, raceway, electric hinge and
pigtail 8-pin connector terminations
and wire colors all match
2. Tape or cap off ends of unused pigtail
wires (not shown) to ensure that they
don’t short to anything
3. A fire alarm tie-in is required on fire
rated openings. If fire alarm is not
required, connect the white wire to the
black (- 24VDC) wire
4. The fire alarm contact could be wired
to drop 24VDC power to rail. In this
case, terminate fire alarm contact
between the red (+ 24VDC) wire and
24VDC output. Connect the
white (FA) wire to the black (- 24VDC)
wire