System Wiring Examples (continued)

Pigtail harness

assembly with

 8-pin connector

Normally Closed Fire

Alarm Contact

(If Required)

Black 

(

-

24), 

1

Red 

(+24), 

2

6, Blue (DS)

White (FA), 3

1

7 5

6 4

3

2

8

Green (EG), 4

C

8

7

4 5

1 2 3

9

6

* 0 #

5, Orange (EI)

(

-

)

NO

(+)

4291

Keypad

(inside)

8, Yellow (RAR - NO)

Brown (RAR - C), 7

Green (NC)

3287

Door status

switch

(-)

4380H

(remote)

horn

(+)

White (C)

RAR contact shown in

rail powered on state

When door is closed,

the green wire is

shorted to white wire

NOTE: This drawing shows  

the BPS Series. The PM Series  

has no line voltage input, fuse  

or connector to power on LED

110-120 VAC

2.5 AMP polyswitch breaker

3520 24VDC 1.0AMP Regulated and Filtered Power Supply

GND

NEUT

HOT

Unconnected

terminal for

switch hookup

Red 

1

2

3

AC

F

AC

Battery pack

Black 

Output

From transformer

Connector

to power on LED

Low voltage AC

DC

DC

Voltage adjust for

battery backup

Line voltage

fuse (1 AMP)

Sample Wiring #2 –  59- Electroguard™ Exit Device with inside Keypad,  

Fire Alarm, Door Status and Remote Horn

A valid code entry at the 4291 (Inside) keypad shunts the Electroguard™ exit device and allows egress for a time period 

programmable at the keypad. During a fire alarm condition, the contact opens which de-energizes the rail electromagnet and allows 

immediate egress. When the rail is armed and the door is forced open, the 3287 door status switch signals the rail sounding the rail 

alarm. When the rail is armed and violated, the remote alarm relay sends 24VDC to the 4380H remote horn.

Plug pigtail harness 

connector into  

8-pin hinge connector 

at frame side of door

Electric hinge with 

8-pin connectors

Raceway harness with 8 & 4-pin 

connectors. The 4-pin connectors 

are not used here

59- 80 Series Rail with  

8 & 4-pin connector. The 

4-pin connector is not  

used here

Note: Typical raceway location is 

shown. Other locations may exist 

depending on door type

Wiring Notes:

1.  Rail, raceway, electric hinge and 

pigtail 8-pin connector terminations 

and wire colors all match

2.  Tape or cap off ends of unused pigtail 

wires (not shown) to ensure that they 

don’t short to anything

3.  A fire alarm tie-in is required on fire 

rated openings. If fire alarm is not 

required, connect the white wire to the 

black (- 24VDC) wire

4.  The fire alarm contact could be wired 

to drop 24VDC power to rail. In this 

case, terminate fire alarm contact 

between the red (+ 24VDC) wire and 

24VDC output. Connect the 

white (FA) wire to the black (- 24VDC) 

wire

A7690C.indd   22

11/8/18   9:02 AM

Summary of Contents for Sargent Electroguard-59 80 Series

Page 1: ...ctions For Electroguard 59 Prefix 80 Series Exit Device to ElectroLynx Connector System For installation assistance contact SARGENT at 800 810 WIRE 9473 A7690C 3 08 SARGENT Manufacturing Company 2008...

Page 2: ...Installation 7 17 Exit Device Plug in Connector Installation 18 Electroguard Input Output Diagram 19 Electrical Specifications 19 Input Output Descriptions 20 System Wiring Examples 21 24 Operating I...

Page 3: ...rd Replacement Kit for F size rails Includes one 52 2558 circuit board and F size rail harness 52 2995 59 Circuit Board Replacement Kit for J size rails Includes one 52 2558 circuit board and J size r...

Page 4: ...s whether the Rail Magnet is energized or de energized Red LED Indicates whether the Push Rail REX Switch is activated or de activated Orange LED Monitors the Door Status Switch position when switch i...

Page 5: ...or other power transfer 1 2 3 4 5 6 7 8 9 0 SARGENT Ordered Separately CAUTION There are no user serviceable parts on the Electroguard Circuit Board Consult parts breakdown for new Electroguard Circu...

Page 6: ...wer is disconnected 2 Separate circuit board and ground wire from mounting insert by removing the four 4 screws from the under side 3 Once separated slide cylinder through collar into the insert as sh...

Page 7: ...nit will go back into the delayed egress mode and the alarm will not sound Nuisance delay is set to On position at factory If the Dip Switch S2 1 is in the Off position there will be no nuisance delay...

Page 8: ...rohibited Inside View of Door Verify hand and bevel of door Exit devices are always reverse bevel and are mounted on the inside of the door On inside of door exit devices are oriented as follows 8800...

Page 9: ...s designed to be installation friendly with pluggable connectors from the electric hinge through the door to the rail The only wiring required is to the loose wires on the pigtail harness assembly on...

Page 10: ...wire colors all match Exit Device Installation continued Installing 59 8300 12 59 8300 Series Mortise Lock Exit Device CAUTION BEFORE STARTING Check hand of door This exit device is handed and not rev...

Page 11: ...ening in chassis for wires Chassis mounting holes Inside of door Chassis arm Wire holder Push rail 1 Feed wire and connector through chassis as shown and mount chassis 2 Depress chassis arm and slide...

Page 12: ...with 2 Fillister head screws Refer to Instruction A6697 NOTE If 700 ET Series Control is used mount ET control next Top case assembly Latch retractor button Top bolt Top rod Inner chassis Bottom rod...

Page 13: ...il wire connector Wire connector Wire holder Guarded latchbolt PREPARE DOOR AND MOUNT HARDWARE Refer to Instruction sheet A6699 Rail assembly Push rail Rail assembly Push rail APPLY STRIKE CRITICAL TO...

Page 14: ...anded and not reversible Door should be fitted and hung Verify box label for size of exit device function and hand IMPORTANT Surface of door where exit device is to be applied must be flush Clear away...

Page 15: ...ner chassis and slide this assembly into the door being careful not to damage wire and connector 2 Slide wire and connector through the wire opening in the door 3 Attach the inner chassis to the door...

Page 16: ...er the slide and then joins the other wire on top of pin 3 Connect ElectroLynx connectors and wire tie wires to the pin as shown 4 Finish installation per instruction sheet A6701 and Section 10 within...

Page 17: ...o allow exit device to rest on flat surface of door Lock Down Key 7 32 hex key To operate Depress pushrail insert hex key and turn clockwise Not furnished with 12 8800 Main Chassis Dwg Chassis 12 8810...

Page 18: ...llustrated Vertical reverse line C L of chassis General Touch Bar Wire connector Mortise lock body CAUTION BEFORE STARTING Check hand of door This device is handed and not reversible Door should be fi...

Page 19: ...nting holes Inside of door 8900 Mortice Lock Dwg 1 Feed wire and connector through chassis as shown 2 Snap the ElectroLynx connectors together and gather excess wire in the top section of the chassis...

Page 20: ...Go to A if wiring now Go to B if wiring is to be done later A Refer to Input Output Terminations Section 11 through Wiring Examples Section 14 Wire to loose wires on pigtail harness es as required us...

Page 21: ...ernal inhibit disarm unit from i s or o s key switch card reader keypad 8 6 J1 5 input Blue Door position sensor Door Status Monitor 8 4 Chassis Ground Green ESD Earth Ground 8 7 J2 1 output Brown Rem...

Page 22: ...2 3 Remote Alarm Relay Output A SPDT Single Pole Double Throw 1A 24VDC contact 8 8 relay is provided for external alarm indication The contacts change state when the unit 4 1 goes into an irreversibl...

Page 23: ...with Fire Alarm During a fire alarm condition the fire alarm contact opens which de energizes the rail magnet and allows immediate egress Plug pigtail harness connector into 8 pin hinge connector at...

Page 24: ...y at the 4291 Inside keypad shunts the Electroguard exit device and allows egress for a time period programmable at the keypad During a fire alarm condition the contact opens which de energizes the ra...

Page 25: ...Exit Device with Fire Alarm Keypads and Fail Safe ET During a fire alarm condition the contact opens which de energizes the rail electromagnet and allows immediate egress A valid code entry at the 42...

Page 26: ...ce Gang is required a connection choice should be made depending on which rail wires are unused leading to the 8 and 4 pin door side electric hinge When determined cut those wires from the door side e...

Page 27: ...time period allowing for momentary egress 3 After the factory preset time of 5 seconds delay expires Rail assembly re arms itself 4 Unit is then in Delayed Egress Mode or Power Up State 1 Rotate key c...

Page 28: ...The alarm will continue to sound until the rail assembly is reset by inserting the key into the cylinder located on the mounting insert and rotating the key clockwise to return the unit to the delaye...

Page 29: ...fix Option The BC prefix for Electroguard indicates that the unit has been programmed to comply with the section of the BOCA code relating to delayed egress BOCA allows for automatic reset of the dela...

Page 30: ...ent cleaning with a product specific for stainless will avoid discoloration and pitting remove any contamination before damage occurs protect with a metal polish or car wax US3 Polished brass US4 Sati...

Page 31: ...EI 5 Blue DS J3 8 pin internal rail harness 1 Blue Mag 2 Green Mag 3 Brown LBM 4 Red LBM 5 6 7 Orange PR 8 Yellow PR J2 9 pin harness 1 Brown RAR C 2 Violet RAR NO 3 Yellow RAR NC 4 Grey LBM C 5 Tan L...

Page 32: ...the latch bolt is retracted about half way the Yellow Diagnostic LED turns ON The LED will be ON from the half way to the fully retracted position otherwise the Led will be OFF 2 With Vertical Rod ty...

Page 33: ...ng connectors at the 59 circuit board Disconnect the 24VDC Power Supply or remove the Red 24VDC power wire at the rail Resistance measurements of the Rail Electromagnet Push Rail and LBM Switches can...

Page 34: ...on the old version circuit board can be used for troubleshooting if the rail will not arm First unplug the LBM switch assembly 2 pin connector from the rail 2 pin connector Next unplug J4 jumper from...

Page 35: ...ire old board is connected to Black wire 24VDC through external device or directly The rail is in fire alarm condition The White wire new board is not connected directly or through a fire alarm contac...

Page 36: ...new construction renovation and replacement applications The company s customer base includes commercial construction institutional and industrial markets SARGENT Manufacturing Company ASSA ABLOY is...

Reviews: