System Wiring Examples (continued)
NOTE: This drawing shows
the BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED
110-120 VAC
2.5 AMP polyswitch breaker
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
GND
NEUT
HO
T
Unconnected
terminal for switch
hookup
Red
1
2
3
AC
F
AC
Battery Pack
Black
Output
From transformer
Connector
to power on LED
Low voltage AC
DC
DC
Voltage adjust for
battery backup
Line voltage
fuse (1 AMP)
Sample Wiring #3 – 59- Electroguard™ Exit Device with Fire Alarm,
Keypads and Fail Safe ET
During a fire alarm condition, the contact opens which de-energizes the rail electromagnet and allows immediate egress. A valid
code entry at the 4291 (Inside) keypad shunts the Electroguard™ exit device and allows egress for a time period programmable at
this keypad. A valid code entry at the 4292 (Outside) keypad unlocks the 773 or 775 Fail Safe ET and shunts the Electroguard™
exit device and allows ingress for a time period programmable at this keypad.
Wiring Notes:
1. Rail, raceway, electric hinge and
pigtail 8-pin connector terminations
and wire colors all match
2. A fire alarm tie-in is required on fire
rated openings. If fire alarm is not
required, connect the white wire to
the black (- 24VDC) wire
3. The fire alarm contact could be
wired to drop 24VDC power to rail.
In this case, terminate the white
(FA) wire to the black (- 24VDC)
wire