ASSA ABLOY Hospitality
66 8003 016-3
11.At
Temperature
display
, choose
between
room temperature
;
default
set temperature
,
i.e. the temperature
which has been set on
the thermostat by
the guest
Figure 55
12.At
Intelligent switch
,
choose between
disabled
; default
use RV output
use G2 output
The intelligent switch is an
output for lighting control
which works according to
the occupancy status.
If intelligent switch is
applicable, normally 'Use
RV output' should be
marked unless the air
handler is a heat pump.
In the latter case, mark
'Use G2 output' instead.
Figure 56
13.If desired, it is possible
to have a
Welcome
scene
which is activated
when the occupancy
state for a room
changes from unsold to
unoccupied. The available
alternatives for welcome
scene are (default is
'disabled'):
disabled
use RV output
use G2 output
14.At
Pulse length
, the
welcome scene can be
set up to have a
pulse length:
0 = welcome scene
always off
chosen length in the
interval 1-255 s
Figure 57