![Asentria Teleboss 850 User Manual Download Page 9](http://html.mh-extra.com/html/asentria/teleboss-850/teleboss-850_user-manual_2981745009.webp)
TeleBoss 850 2.06.280_STD User Manual
Page 3
3.
Using wire nuts (not supplied), connect the stripped wires to the power source. The red wires connect to ground
or the most Positive connection on the voltage source. The blue wires connect to -48VDC or the most Negative
connection on the voltage source.
Option B:
Use the supplied kit to make a wire harness:
1.
You will need a crimping tool that crimps standard Molex type 18-24 AWG Mini-Fit Terminals (Molex Part
Number: 39-00-0060, Engineering Series 5556).
2.
Crimp the supplied terminals to your cable connections.
3.
Insert the crimped terminals into the supplied white nylon housing. Orient the housing so the latching mechanism
is up and you are looking into the large end of the housing. See diagram above. Insert the 2 Ground or Most
Positive leads into the upper and lower compartments on the left side of the connector, e.g. the same positions as
the red wires on the supplied harness assembly. Insert the 2 -48VDC or Most Negative leads into the upper and
lower compartments on the right side of the connector, e.g. the same positions as the blue leads on the supplied
harness assembly.
4.
Connect the completed assembly into the power input receptacle at the rear of the unit.
Accessing the Command Line via a Serial Connection
1. Connect to I/O 2 with a serial terminal emulation program at 19200 baud, 8N1.
2. Enter
STATUS
or
?
and press <Enter>. You will be presented with a status screen similar to the following.
TeleBoss 850 2.06.280 STD - Status
Site Name : 850-850000163
Serial Number : 850000163 Eth 1 : STATIC
Date : THU 03/03/2011 IP Addr : 0.0.0.0
Time : 08:02:48 MAC Addr : 00:10:A3:60:02:3E
Memory : 32768K Eth 2 : STATIC
% Full Alarm : OFF IP Addr : 0.0.0.0
No-Data Alarm 1 : OFF MAC Addr : 00:10:A3:60:02:3F
No-Data Alarm 2 : OFF Modem : Yes
Duplex : FULL
-------------------------------------------------------------------------
Port Baud/Etc. Recs Bytes Full Wrap Name
IO1 : 19200,8N1 00000000 00000000 0% OFF I/O 1
IO2 : 19200,8N1 00000000 00000000 0% OFF I/O 2
COMPLETE
>
When the status screen appears, the unit is successfully connected and ready for use.
Accessing the Command Line via the Asentria OmniDiscover program
1. From the Asentria website (
http://www.asentria.com/docsandsoftware/productManuals.aspx
), or the
Documentation and Utilities CD, download the OmniDiscover program. This program will allow you to locate
devices on your network (ie: the T850) with Asentria MAC addresses, and allow you to assign the network
settings directly over the network, thus eliminating the need for the serial port connection as described above.
2. Open the OmniDiscover program. It will immediately display all Asentria devices on the network. Right clicking
on the line for this unit displays three options: Setup, Telnet and Web.
Setup
opens another window where the IP Address, Subnet Mask, and Gateway (router) can be configured
(see below). Press “OK” and these will be assigned to the unit and displayed in the previous window. (Select
this option to configure the network settings for the first time.)
Telnet
opens a connection to the device using your default Telnet client.
Summary of Contents for Teleboss 850