![Asentria Teleboss 850 User Manual Download Page 130](http://html.mh-extra.com/html/asentria/teleboss-850/teleboss-850_user-manual_2981745130.webp)
TeleBoss 850 2.06.280_STD User Manual
Page 124
Very High Event Temperature
sets the temperature at which the Very High Event Actions will be triggered.
Very High Event Actions
displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Very High Trap Number
sets the trap number which can be useful when using SNMP trap managers that employ a
trap numbering system to help identify incoming traps. The default trap number for Temperature Events is 120, but
any number in the alternate range of 1000
– 1199 can be used.
Very High Event Class
sets the class for the alarm. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings Setup
TeleBoss 850 - Internal Temperature Event Settings
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [120]
C) Return to Normal Class [Info]
Return to Normal Event Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to
in the Features chapter for more information.
Return to Normal Event Trap Number
sets the trap number which can be useful when using SNMP trap managers
that employ a trap numbering system to help identify incoming traps. The default trap number for Temperature Events
is 120, but any number in the alternate range of 1000
– 1199 can be used.
Return to Normal Class
sets the class for the alarm. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Humidity Sensor Setup
TeleBoss 850 - Internal Humidity Event
A) Humidity Sensor Enabled [OFF]
B) Humidity Deadband [3]
C) Very High Event Settings [90] [] [130] [Info]
D) High Event Settings [80] [] [130] [Info]
E) Return to Normal Settings [-] [] [130] [Info]
F) Low Event Settings [20] [] [130] [Info]
G) Very Low Event Settings [10] [] [130] [Info]
Humidity Sensor Enabled
is an ON/OFF toggle to enable the humidity sensor. Default setting is OFF.
Humidity Deadband
is the range on either side of a humidity setting that prevents the alarm from repeatedly going in
and out off the "alarm state" as the actual humidity fluctuates above and below the humidity setting.
Very High / High / Low / Very Low Event Settings
display a menu where the humidity at each level can be
configured to alarm along with the action(s) to occur, trap number, and class. In the case of Very High or High levels,
the alarm will occur as the humidity rises above the setting. In the case of Low or Very Low, the alarm will occur as
the humidity drops below the setting.
displays a menu where the actions to occur when the humidity returns to normal (drops
below the High/Very High settings, or rises above the Low/Very Low settings) can be configured.
Summary of Contents for Teleboss 850
Page 6: ......