TeleBoss 850 2.06.280_STD User Manual
Page 123
Event State
is an OPEN/CLOSED toggle that determines whether an event will be triggered when the contact closure
circuit is opened or closed. The default state is OPEN.
Threshold
is the number of seconds (0-255) the sensor must remain in the event state before an actual event occurs.
Default threshold is 2.
Event State / Return to Normal Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to
in the Features chapter for more information.
Event State / Return to Normal Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.
Event / Return to Normal Trap Number
sets the trap number which can be useful when using SNMP trap managers
that employ a trap numbering system to help identify incoming traps. The default trap number for Contact Closure
Events is 110, but any number in the alternate range of 1000
– 1199 can be used.
Active Alarm Alias
is a special sensor name used when reporting active events for this sensor.
Inactive Alarm Alias
is the same as Active Alarm Alias, but used with Return to Normal events.
Temperature Sensor Setup
TeleBoss 850 - Internal Temperature Event
A) Temperature Sensor Enabled [OFF]
B) Sensor Values Represented in [FAHRENHEIT]
C) Temperature Deadband [3]
D) Very High Event Settings [100] [] [120] [Info]
E) High Event Settings [80] [] [120] [Info]
F) Return to Normal Settings [-] [] [120] [Info]
G) Low Event Settings [50] [] [120] [Info]
H) Very Low Event Settings [30] [] [120] [Info]
Temperature Sensor Enabled
is an ON/OFF toggle to enable the temperature sensor. Default setting is OFF.
Sensor Values Represented In
toggles either FAHRENHEIT or CELSIUS for the desired temperature scale.
Temperature Deadband
is the range, in degrees, on either side of a temperature setting that prevents the alarm from
repeatedly going in and out of the "alarm state" as the actual temperature fluctuates above and below the temperature
setting.
Very High / High / Low / Very Low Event Settings
display a menu where the temperature at each level can be
configured to alarm along with the action(s) to occur, trap number, and class. In the case of Very High or High levels,
the alarm will occur as the temperature rises above the setting. In the case of Low or Very Low, the alarm will occur
as the temperature drops below the setting.
displays a menu where the actions to occur when the temperature returns to normal
(drops below the High/Very High settings, or rises above the Low/Very Low settings) can be configured.
Very High / High / Low / Very Low Event Settings Setup
TeleBoss 850 - Internal Temperature Event Settings
A) Very High Event Temperature [100]
B) Very High Event Actions []
C) Very High Event Trap Number [120]
D) Very High Event Class [Info]
The menu for setting Very High Temperature settings is shown. Menus for High/Low/Very Low are identical.