![Asentria Teleboss 850 User Manual Download Page 37](http://html.mh-extra.com/html/asentria/teleboss-850/teleboss-850_user-manual_2981745037.webp)
TeleBoss 850 2.06.280_STD User Manual
Page 31
Serial Settings
TeleBoss 850 - Serial Settings
A) 1-I/O 1 Settings
B) 2-I/O 2 Settings
Note:
Because I/O2 has all the settings the other serial ports have, plus a few more, it will be described in the
section below with differences in other ports mentioned when necessary.
Serial Port Menu
TeleBoss 850 - Serial 2
A) Target Name [I/O 2]
B) Baud Rate [19200]
C) Data Format [8N1]
D) Handshaking [NONE]
E) Wrap Around [OFF]
F) Record Stamping
G) Character Masking [ON]
H) Data Alarm Enable [OFF]
I) Store Data To [2]
J) Store Alarms During Pass-Through [OFF]
K) Duplex [FULL]
L) Inactivity Timeout [0]
M) Port Mode [COMMAND]
N) Inline Mode Handshaking [XON/XOFF]
O) Strip Sent Pass-Through LFs [OFF]
P) Strip Received Pass-Through LFs [OFF]
Q) Disable Serial Setup via DIP Switch [OFF]
R) Multiline Record Settings [OFF]
S) Data Type [ASCII]
T) Change ETX to CR/LF [OFF]
Target Name
is the name given to the device connected to the other end of each port. The target name is used in
event notifications. Default setting is I/O n. (Max length is 24 chars)
Baud Rate
displays a selection menu for baud rates available for the port. These values range from 300 baud to
115200 baud. Default setting is 19200.
Data Format
toggles settings for word length, parity, and stop bit settings. The available options are: 8N1, 7E1, 7O1,
7N1, and 8O2. Default setting is 8N1.
Handshaking
is a toggle item with the following options: None, Xon/Xoff, Both, and DTR. Default setting is None.
Wrap Around
is an ON/OFF toggle to set whether the incoming data will wrap (overwrite) the oldest data in the file
should it become full. Default setting is OFF.
Record Stamping
displays a menu that allows you to select whether the Date/Time and/or the Unit ID are pre-pended
to each incoming data string. Default setting for Date/Time and Unit ID is OFF.
Character Masking
is an ON/OFF toggle to enable the character mask. The character mask allows you to block
most non-printing ASCII characters. Specifically, the following ASCII character values are blocked: 0, 1, 4-9, 11, 12,
14-31, and 128-255. Default setting is ON.
Data Alarm Enable
is an ON/OFF toggle to enable data alarm monitoring for this port. Default setting is OFF.
Store Data To
displays a menu that allows you to toggle ON/OFF the files to which incoming data on this port should
be stored, if any.