P44x/EN AP/E33
Application Notes
Page 90/220
MiCOM P441/P442 & P444
2.19 Undervoltage
protection
Undervoltage conditions may occur on a power system for a variety of reasons, some of
which are outlined below:-
•
Increased system loading. Generally, some corrective action would be taken by
voltage regulating equipment such as AVR’s or On Load Tap Changers, in order to
bring the system voltage back to it’s nominal value. If the regulating equipment is
unsuccessful in restoring healthy system voltage, then tripping by means of an
undervoltage relay will be required following a suitable time delay.
•
Faults occurring on the power system result in a reduction in voltage of the phases
involved in the fault. The proportion by which the voltage decreases is directly
dependent upon the type of fault, method of system earthing and its location with
respect to the relaying point. Consequently, co-ordination with other voltage and
current-based protection devices is essential in order to achieve correct discrimination.
This function will be blocked with VTS logic or could be disabled if CB open.
Both the under and overvoltage protection functions can be found in the relay menu “Volt
Protection”. The following table shows the undervoltage section of this menu along with the
available setting ranges and factory defaults.
Menu text
Default setting
Setting range
Step size
Min
Max
GROUP 1
VOLT Protection
V< & V> MODE
0
V<1 Trip, V<2 Trip, V>1 Trip, V>2 Trip
UNDER VOLTAGE
V< Measur't Mode
Phase-Neutral
Phase-phase or Phase-neutral
V<1 Function
DT
Disabled, DT pr IDMT
V<1 Voltage Set
50V
10V
120V
1V
V<1 Time Delay
10s
0s
100s
0.01s
V<1 TMS
1
0.5
100
0.5
V<2 Status
Disabled
Disabled or Enabled
V<2 Voltage Set
38V
10V
120V
1V
V<2 Time Delay
5s
0s
100s
0.01s
As can be seen from the menu, the undervoltage protection included within the P441, P442
and P444 relays consists of two independent stages. These are configurable as either
phase to phase or phase to neutral measuring within the V< Measur’t Mode cell.
Stage 1 may be selected as either IDMT, DT or disabled, within the V<1 Function cell.
Stage 2 is DT only and is enabled/disabled in the V<2 Status cell.
Two stages are included to provide both alarm and trip stages, where required.
Alternatively, different time settings may be required depending upon the severity of the
voltage dip.
The IDMT characteristic available on the first stage is defined by the following formula:
t =
K
1 – M
Where:
K
=
Time Multiplier Setting (TMS)
T
=
Operating Time in Seconds
M
=
Measured Voltage / relay Setting Voltage (V<)
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......