2.15
Negative sequence overcurrent protection (NPS)
When applying traditional phase overcurrent protection, the overcurrent elements must be
set higher than maximum load current, thereby limiting the element’s sensitivity. Most
protection schemes also use an earth fault element operating from residual current, which
improves sensitivity for earth faults. However, certain faults may arise which can remain
undetected by such schemes.
Any unbalanced fault condition will produce negative sequence current of some magnitude.
Thus, a negative phase sequence overcurrent element can operate for both phase-to-phase
and phase to earth faults.
The following section describes how negative phase sequence overcurrent protection may
be applied in conjunction with standard overcurrent and earth fault protection in order to
alleviate some less common application difficulties.
•
Negative phase sequence overcurrent elements give greater sensitivity to resistive
phase-to-phase faults, where phase overcurrent elements may not operate.
•
In certain applications, residual current may not be detected by an earth fault relay
due to the system configuration. For example, an earth fault relay applied on the delta
side of a delta-star transformer is unable to detect earth faults on the star side.
However, negative sequence current will be present on both sides of the transformer
for any fault condition, irrespective of the transformer configuration. Therefore, an
negative phase sequence overcurrent element may be employed to provide time-
delayed back-up protection for any uncleared asymmetrical faults downstream.
•
Where rotating machines are protected by fuses, loss of a fuse produces a large
amount of negative sequence current. This is a dangerous condition for the machine
due to the heating effects of negative phase sequence current and hence an upstream
negative phase sequence overcurrent element may be applied to provide back-up
protection for dedicated motor protection relays.
•
It may be required to simply alarm for the presence of negative phase sequence
currents on the system. Operators may then investigate the cause of the unbalance.
The negative phase sequence overcurrent element has a current pick up setting ‘I2> Current
Set’, and is time delayed in operation by the adjustable timer ‘I2> Time Delay’. The user
may choose to directionalise operation of the element, for either forward or reverse fault
protection for which a suitable relay characteristic angle may be set. Alternatively, the
element may be set as non-directional.
2.15.1 Setting
Guidelines
The relay menu for the negative sequence overcurrent element is shown below:
NEG SEQ O/C
Default
Min
Max
Step
I2> Status
Enabled
Disabled, Enabled
I2> Directional
Non-Directional Non-Directional,
Directional Fwd, Directional Rev
I2> VTS
Non-Directionel
Block, Non-Directional
I2> Current Set
0.2In 0.08In 4In
0.01In
I2> Time Delay
10s
0s
100s
0.01s
I2> Char Angle
–45
°
–95
°
+95
°
1
°
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......