P44x/EN AP/E33
Application Notes
Page 84/220
MiCOM P441/P442 & P444
SBEF Trip
SBEF
Overcurrent
CTS Block
SBEF Trip
P0484ENa
SBEF Timer Block
SBEF Start
IDMT/DT
FIGURE 45 - LOGIC WITHOUT DIRECTIONALITY
SBEF Trip
SBEF
Overcurrent
CTS Block
P0533ENa
SBEF Timer Block
SBEF Start
Vx > Vs
Ix > Is
Slow VTS
Block
IDMT/DT
Directional
Check
FIGURE 46 - LOGIC WITH DIRECTIONALITY
2.17.1
Directional Earth Fault Protection (DEF)
The method of directional polarising selected is common to all directional earth fault
elements, including the channel-aided element. There are two options available in the relay
menu:
•
Zero sequence polarising - The relay performs a directional decision by comparing
the phase angle of the residual current with respect to the inverted residual voltage:
(–Vres = –(Va + Vb + Vc)) derived by the relay.
•
Negative sequence polarising - The relay performs a directional decision by
comparing the phase angle of the derived negative sequence current with respect to
the derived negative sequence voltage.
NOTE:
Even though the directional decision is based on the phase
relationship of I
2
with respect to V
2
, the operating current quantity for
DEF elements remains the derived residual current.
2.17.2
Application of Zero Sequence Polarising
This is the conventional option, applied where there is not significant mutual coupling with a
parallel line, and where the power system is not solidly earthed close to the relay location.
As residual voltage is generated during earth fault conditions, this quantity is commonly used
to polarise DEF elements. The relay internally derives this voltage from the 3 phase voltage
input which must be supplied from either a 5-limb or three single phase VT’s. These types of
VT design allow the passage of residual flux and consequently permit the relay to derive the
required residual voltage. In addition, the primary star point of the VT must be earthed. A
three limb VT has no path for residual flux and is therefore incompatible with the use of zero
sequence polarising.
The required characteristic angle settings for DEF will differ depending on the application.
Typical characteristic angle settings are as follows:
•
Resistance earthed systems generally use a 0
°
RCA setting. This means that for a
forward earth fault, the residual current is expected to be approximately in phase with
the inverted residual voltage (-Vres).
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......