P44x/EN AP/E33
Application Notes
Page 80/220
MiCOM P441/P442 & P444
2.16
Broken conductor detection
The majority of faults on a power system occur between one phase and ground or two
phases and ground. These are known as shunt faults and arise from lightning discharges
and other overvoltages which initiate flashovers. Alternatively, they may arise from other
causes such as birds on overhead lines or mechanical damage to cables etc. Such faults
result in an appreciable increase in current and hence in the majority of applications are
easily detectable.
Another type of unbalanced fault which can occur on the system is the series or open circuit
fault. These can arise from broken conductors, maloperation of single phase switchgear, or
the operation of fuses. Series faults will not cause an increase in phase current on the
system and hence are not readily detectable by standard overcurrent relays. However, they
will produce an unbalance and a resultant level of negative phase sequence current, which
can be detected.
It is possible to apply a negative phase sequence overcurrent relay to detect the above
condition. However, on a lightly loaded line, the negative sequence current resulting from a
series fault condition may be very close to, or less than, the full load steady state unbalance
arising from CT errors, load unbalance etc. A negative sequence element therefore would
not operate at low load levels.
The relay incorporates an element which measures the ratio of negative to positive phase
sequence current (I
2
/I
1
). This will be affected to a lesser extent than the measurement of
negative sequence current alone, since the ratio is approximately constant with variations in
load current. Hence, a more sensitive setting may be achieved.
2.16.1 Setting
Guidelines
The sequence network connection diagram for an open circuit fault is detailed in Figure 1.
From this, it can be seen that when a conductor open circuit occurs, current from the positive
sequence network will be series injected into the negative and zero sequence networks
across the break.
In the case of a single point earthed power system, there will be little zero sequence current
flow and the ratio of I2/I1 that flows in the protected circuit will approach 100%. In the case of
a multiple earthed power system (assuming equal impedances in each sequence network),
the ratio I2/I1 will be 50%.
It is possible to calculate the ratio of I2/I1 that will occur for varying system impedances, by
referring to the following equations:-
I
1F
=
E
g
(Z
2
+ Z
0
)
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
I
2F
=
–E
g
Z
0
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
Where:
E
g
=
System
Voltage
Z
0
=
Zero
sequence
impedance
Z
1
=
Positive sequence impedance
Z
2
= Negative
sequence
impedance
Therefore:
I
2F
I
1F
=
Z
0
Z
0
+ Z
2
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......