Application Notes
P44x/EN AP/E33
MiCOM P441/P442 & P444
Page 123/220
4.4.5
Logic inputs / Outputs from synchrocheck function
4.4.5.1
Logic DDB input from the check sync logic
MCB/VTS Bus
The DDB:MCB/VTS Bus if assigned to an opto input in PSL and when energized, will inform
the P44X about an internal maloperation from the VT used for synchrocheck ref. (BUS in
that case means Checksync ref measurement / even if the main VT is on the bus side and
the Synchro VT is on the line side)
When this opto picks up it will block the internal logic of Synchrocheck.
MCB/VTS Line
The DDB:MCB/VTS Line if assigned to an opto input in PSL and when energized, will inform
the P44X about an internal maloperation from the VT used for impedance measurement ref.
(Line in that case means Main VT ref measurement / even if the main VT are bus side and
the Synchro VT is line side)
When that opto picks up it will block the internal logic of Synchrocheck.
4.4.5.2
Logic DDB outputs issued by the check sync logic
Check Sync OK
Set high when Check Synchro conditions are verified
[Used with AR close in dedicated PSL – "AND" gate : [(AR Close) & (CheckSync OK)]
A/R Force Sync
Simulates the CheckSync control and force the logical DDB output "CheckSync OK" at 1
during a 1 pole or 3 poles high speed AR cycle. Without CheckSync control (See the
explanation in AR description Figure 76 and Figure 106)
V<Dead Line
Set high when the Dead line condition is verified (voltage below the V<Dead Line threshold
value (settable in MiCOM S1) – The measured voltage is always calculated as a single
phase voltage
V>Live Line
Set high when the Live line condition is verified (voltage above the V>Live Line threshold
value (settable in MiCOM S1) - always calculated as a single phase voltage ref
V<Dead Bus
Set high when the Dead Bus condition is verified (voltage below the V<Dead Bus threshold
value (settable in MiCOM S1) - always calculated as a single phase voltage ref
V>Live Bus
Set high when the Live Bus condition is verified (voltage above the V>Live Bus threshold
value (settable in MiCOM S1) - always calculated as a single phase voltage ref
Control No C/S
Set high when the internal Check Sync conditions are not verified
Ext Chk Synch OK
The DDB Ext Chk Synch OK if assigned to an opto input in PSL and when energized,
indicates that Check Sync conditions are verified by an external device – The DDB cell
should be assigned afterwards with an internal AR logic (See also AR description in section
4.5.1).
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......