Application Notes
P44x/EN AP/E33
MiCOM P441/P442 & P444
Page 75/220
2.14.1
Application of Timer Hold Facility
The first two stages of overcurrent protection in the P441, P442 and P444 relays are
provided with a timer hold facility, which may either be set to zero or to a definite time value.
(Note that if an IEEE/US operate curve is selected, the reset characteristic may be set to
either definite or inverse time in cell I>1 Reset Char; otherwise this setting cell is not visible
in the menu). Setting of the timer to zero means that the overcurrent timer for that stage will
reset instantaneously once the current falls below 95% of the current setting. Setting of the
hold timer to a value other than zero, delays the resetting of the protection element timers for
this period. This may be useful in certain applications, for example when grading with
upstream electromechanical overcurrent relays which have inherent reset time delays.
Another possible situation where the timer hold facility may be used to reduce fault clearance
times is where intermittent faults may be experienced. An example of this may occur in a
plastic insulated cable. In this application it is possible that the fault energy melts and reseals
the cable insulation, thereby extinguishing the fault. This process repeats to give a
succession of fault current pulses, each of increasing duration with reducing intervals
between the pulses, until the fault becomes permanent.
When the reset time of the overcurrent relay is instantaneous the relay may not trip until the
fault becomes permanent. By using the timer hold facility the relay will integrate the fault
current pulses, thereby reducing fault clearance time.
Note that the timer hold facility should not be used where high speed autoreclose with short
dead times are set.
The timer hold facility can be found for the first and second overcurrent stages as settings
I>1 tRESET and I>2 tRESET. Note that this cell is not visible if an inverse time reset
characteristic has been selected, as the reset time is then determined by the programmed
time dial setting.
2.14.2
Directional Overcurrent Protection
If fault current can flow in both directions through a relay location, it is necessary to add
directional control to the overcurrent relays in order to obtain correct discrimination. Typical
systems which require such protection are parallel feeders and ring main systems. Where
I>1 or I>2 stages are directionalised, no characteristic angle needs to be set as the relay
uses the same directionalising technique as for the distance zones (fixed superimposed
power technique).
2.14.3
Time Delay VTS
Should the Voltage Transformer Supervision function detect an ac voltage input failure to the
relay, such as due to a VT fuse blow, this will affect operation of voltage dependent
protection elements. Distance protection will not be able to make a forward or reverse
decision, and so will be blocked. As the I>1 and I>2 overcurrent elements in the relay use
the same directionalising technique as for the distance zones, any directional zones would
be unable to trip.
To maintain protection during periods of VTS detected failure, the relay allows an I> Time
Delay VTS to be applied to the I>1 and I>2 elements. On VTS pickup, both elements are
forced to have non-directional operation, and are subject to their revised definite time delay.
2.14.4 Setting
Guidelines
I>1 and I>2 Overcurrent Protection
When applying the overcurrent or directional overcurrent protection provided in the P441,
P442 and P444 relays, standard principles should be applied in calculating the necessary
current and time settings for co-ordination. For more detailed information regarding
overcurrent relay co-ordination, reference should be made to AREVA’s ‘Protective relay
Application Guide’ - Chapter 9. In general, where overcurrent elements are set, these
should also be set to time discriminate with downstream and reverse distance protection.
The I>1 and I>2 elements are continuously active. However tripping is blocked if the
distance protection function starts. An example is shown in Figure 42.
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......