(5)
VA = Z1 [IA + kZ0 IR]
(6)
Z1 = VA/(IA + kZ0 IR)
Particular case
Resistive fault
(7)
VA = Z1 [IA + kZ0 IR] + Rdef. Idef (Rdef
=
Rloop)
To determine the distance, Z1 term is extracted.
(8)
Z1 = (VA – Rdef. Idef)/(IA + kZ0 IR)
with
Rdef: fault resistance (loop)
Idef: current crossing the fault resistance
Open line:
Ifault = IR = IA
(9)
VA = Z1 IA (1 + kZ0) + Rfault IA
(10)
Z1 = (VA/IA – Rfault)/(1 + kZ0)
The impedance detected will be:
Z = Z1 (1 + kZ0) + Rfault
That is the form used for the result of Z measured with injector providing U, I,
ϕ
Separate compensation for each zone (KZ1, KZ2, KZ3/4 and KZp) allows more accurate
earth fault reach control for elements which are set to overreach the protected line, such that
they cover other circuits which may have different zero sequence to positive sequence
impedance ratios (Example: underground cable & overhead line in the protected line).
2.7.6
Resistive Reach Calculation - Phase Fault Elements
In MiCOM S1 all resistances are set per loop
The P441, P442 and P444 relays have quadrilateral distance elements, thus the resistive
reach (RPh) is set independently of the impedance reach along the protected line/cable.
RPh defines the maximum amount of fault resistance additional to the line impedance for
which a distance zone will trip, regardless of the location of the fault within the zone. Thus,
the right hand and left hand resistive reach constraints of each zone are displaced by +RPh
and -RPh either side of the characteristic impedance of the line, respectively. RPh is
generally set on a per zone basis, using R1Ph, R2Ph and RpPh. Note that zones 3 and 4
share the resistive reach R3Ph-R4Ph.
When the relay is set in primary impedance terms, RPh must be set to cover the maximum
expected phase-to-phase fault resistance. In general, RPh must be set greater than the
maximum fault arc resistance for a phase-phase fault, calculated as follows:
R
a
=
(28710 x L) / I
f
1.4
RPh
≥
R
a
Where:
I
f
=
Minimum expected phase-phase fault current (A);
L
=
Maximum phase conductor separation (m);
R
a
=
Arc resistance, calculated from the van Warrington formula (
Ω
).
Summary of Contents for MiCOM P441
Page 1: ...MiCOM P441 P442 P444 Numerical Distance Protection VC2 x Technical Guide P44x EN T E44...
Page 2: ......
Page 4: ...P44x EN T E44 Technical Guide Page 2 2 MiCOM P441 P442 P444 BLANK PAGE...
Page 5: ...Pxxxx EN SS C11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS C11 Page 2 10 Safety Section BLANK PAGE...
Page 17: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 UPDATE DOCUMENTATION VERSION C2 X...
Page 18: ......
Page 22: ...P44x EN AD E44 Update Documentation Page 4 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 23: ...Update Documentation P44x EN AD E44 MiCOM P441 P442 P444 Page 5 82 P44X EN IT E33 INTRODUCTION...
Page 24: ......
Page 34: ......
Page 44: ......
Page 96: ...P44x EN AD E44 Update Documentation Page 78 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 98: ......
Page 100: ...P44x EN AD E44 Update Documentation Page 82 82 MiCOM P441 P442 P444 BLANK PAGE...
Page 101: ...Introduction P44x EN IT E33 MiCOM P441 P442 P444 INTRODUCTION...
Page 102: ......
Page 104: ...P44x EN IT E33 Introduction Page 2 24 MiCOM P441 P442 P444 BLANK PAGE...
Page 127: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 RELAY DESCRIPTION...
Page 128: ......
Page 132: ...P44x EN HW E33 Relay Description Page 4 44 MiCOM P441 P442 P444 BLANK PAGE...
Page 152: ...P44x EN HW E33 Relay Description Page 24 44 MiCOM P441 P442 P444 Example isolated AC fault...
Page 153: ...Relay Description P44x EN HW E33 MiCOM P441 P442 P444 Page 25 44...
Page 173: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 APPLICATION NOTES...
Page 174: ......
Page 180: ...P44x EN AP E33 Application Notes Page 6 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 357: ...Application Notes P44x EN AP E33 MiCOM P441 P442 P444 Page 183 220...
Page 364: ...P44x EN AP E33 Application Notes Page 190 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 394: ...P44x EN AP E33 Application Notes Page 220 220 MiCOM P441 P442 P444 BLANK PAGE...
Page 395: ...Technical Data P44x EN TD E33 MiCOM P441 P442 P444 TECHNICAL DATA...
Page 396: ......
Page 400: ...P44x EN TD E33 Technical Data Page 4 30 MiCOM P441 P442 P444 BLANK PAGE...
Page 427: ...Installation P44x EN IN E33 MiCOM P441 P442 P444 INSTALLATION...
Page 428: ......
Page 430: ...P44x EN IN E33 Installation Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 438: ...P44x EN IN E33 Installation Page 10 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 439: ...Commissioning P44x EN CM E33 MiCOM P441 P442 P444 COMMISSIONING...
Page 440: ......
Page 494: ...P44x EN CM E33 Commissioning Page 54 54 MiCOM P441 P442 P444 BLANK PAGE...
Page 496: ......
Page 498: ...P44x EN RS E33 Commissioning Test Record Sheets Page 2 10 MiCOM P441 P442 P444 BLANK PAGE...
Page 507: ...Connection Diagrams P44x EN CO E33 MiCOM P441 P442 P444 CONNECTION DIAGRAMS...
Page 508: ......
Page 510: ...P44x EN CO E33 Connection Diagrams Page 2 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 520: ...P44x EN CO E33 Connection Diagrams Page 12 12 MiCOM P441 P442 P444 BLANK PAGE...
Page 521: ...Courrier Data Base P44x EN GC E44 MiCOM P441 P442 P444 CONFIGURATION MAPPING...
Page 610: ...Courier Data Base P44x EN GC E44 MiCOM P441 P442 P444 DEFAULT PROGRAMMABLE SCHEME LOGIC PSL...
Page 615: ...Menu Content Tables P44x EN HI E44 MiCOM P441 P442 P444 MENU CONTENT TABLES...
Page 616: ......
Page 624: ......
Page 626: ......
Page 634: ...P44x EN VC E44 Hardware Software Version Page 8 8 MiCOM P441 P442 P444 BLANK PAGE...
Page 635: ......