— Page 88 —
© 2011 Aqua-Hot
®
AHE-100-02S Hydronic Heating System Service Manual—Rev. B
A
PPENDIX
D: E
XTREME
C
OLD
W
EATHER
O
PERATION
If there is a lack of interior Heat:
1. Is the Diesel Burner activated?
2. Is the Diesel Burner operating Properly?
3. What is the antifreeze concentration, inside of the
Aqua-Hot Boiler Tank?
4. Was the heating system properly installed, following the
Aqua Hot installation manual?
A. Are there at least 5 heat exchangers installed in the
Interior of the motor home?
B. Are there cold air returns installed for every heat
exchanger? Reference Figure D2
C. Are the heat exchangers mounted as close to the
hot air outlet grill as possible? Reference
Figure D2.
Note:
The 120 Volt-AC Electric Heating Element is
the Aqua-Hot’s
secondary heat source
for heating both
the interior and/or the domestic hot water during low heat-
ing demand situations (such as when moderate ambient
temperatures exist and/or when there is a low demand for
domestic hot water). If the ambient temperature is ex-
Figure D2
Figure D3