CONDENSATION BOILER
AQUAKOND AKY
25
code HC0048.01GB ed.B-1406
AKY
Included at delivery.
Already installed on the boiler.
To be installed by the installer
Fuel shut-off valve - Optional -
C09073
AKY050/070 Installation Scheme
Apen Group equipped its AKY050/070 boilers with a well for housing a sensing bulb and offers C09073 kit on demand.
R
EMARK: If the fuel shut-off valve is exposed to temperatures as low as 0°C, the antifreeze feature of CPU-SMART
board is to be mandatorily enabled (parameter D8=1) to avoid the triggering of sensitive bulb.
LEGEND
1 Main burner gas solenoid valve
2 Pressure stabilizer
3 Safety solenoid valve
4 Gas filter on gal valve (small section)
5 Gas cock (supplied by APEN GROUP)
6 Vibration damping joint
7 Gas filter
8 Fuel detection valve
AKY032/034 Installation Diagram
Included at delivery.
Already installed on the boiler.
To be installed by the
installer
5.6. Gas Connections
For this system, use CE-approved and certified components only.
At delivery AKY boilers include:
•
Double gas valve
•
Gas stabilizer
•
Gas cock
All components are assembled into the boiler but the cock
To complete installation in compliance with the law, the following components have to be installed:
•
Vibration damping joint
•
Gas filter (no stabilizer)
REMARK: Do not use threaded joints directly on gas fitting.
Summary of Contents for AQUAKOND AKY
Page 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Page 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Page 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Page 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...