INSTRUCTIONS TO SERVICE STAFF
First start-up must be performed by an APEN GROUP Authorized Service Centre.
During first start up, the combustion efficiency must be analyzed.
This appliance is certified for EC and Extra-EC countries for the gas categories listed below.
6.1. Country Table - Gas Category
On the packaging of each equipment the following is clearly marked: Destination Country, gas category, and appliance code
translated into the language of destination Country.
The code shows the factory setting for the unit:
Codes without extension:
•
AKY070IT
no extension means that the unit has been prepared and tested for
OPERATION MODES gas [G20]
Codes with extension:
the fourth letter identifies the gas for which the unit has been set:
•
AKY070FR-xxx
0
0 indicates the unit has been set and tested for natural gas [G20]
•
AKY070MT-xxx
1
1 indicates the unit has been set and tested for Liquid Propane [G31]
•
AKY070NL-xxx
2
2 indicates the unit has been set and tested for natural gas [G25]
•
AKY070HU-xxx
3
3 indicates the unit has been set and tested for natural gas [G25.1]
Another label on the unit, placed near fuel supply, clearly states which gas type and supply pressure the unit has been set and
tested for.
Country
Category
Gas
Pressure
Gas
Pressure
AT
II2H3B/P
G20
20 mbar
G30/G31
50 mbar
BE <70kW
I2E(S)B, I3P
G20/G25
20/25 mbar
G31
37 mbar
CH
II2H3B/P
G20
20 mbar
G30/G31
50 mbar
DE
II2ELL3B/P
G20/G25
20 mbar
G30/G31
50 mbar
DK, FI, GR, SE, NO
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
ES, GB, IE, PT, SK
II2H3P
G20
20 mbar
G31
37 mbar
IT, CZ
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
FR
II2Esi3P
G20/G25
20/25 mbar
G31
37 mbar
LU
II2E3P
G20/G25
20 mbar
G31
37/50 mbar
NL
II2L3B/P
G25
25 mbar
G30/G31
50 mbar
HU
II2HS3B/P
G20/G25.1
25 mbar
G30/G31
30 mbar
CY, MT
I3B/P
G30/G31
30 mbar
EE, LT, SI, AL, MK
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
LV
I2H
G20
20 mbar
IS
I3P
G31
37 mbar
BG, RO, HR, TR
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
PL
II2E3B/P
G20
20 mbar
G30/G31
37 mbar
Summary of Contents for AQUAKOND AKY
Page 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Page 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Page 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Page 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...