CONDENSATION BOILER
AQUAKOND AKY
26
code HC0048.01GB ed.B-1406
AKY
Rain protec-
tion
Hole for flue analysis
HC0047 IM 004
HC0047 C2 028
Lm
ax
5.7. Flue Piping
The outdoor unit is supplied with a flue outlet (B23P type) in
white polypropylene that consists of:
•
Rain shelter for air intake
•
One 90° bend Ø60
•
A flue terminal Ø60 with well for flue analysis.
The boiler has an NTC sensor on flue outlet and a thermal
cut-out on the exchanger, to protect polypropylene flue pipe.
The boiler exhaust can be installed directly through the wall.
If exhaust is through the roof, the following accessories can
be used:
G15821-06-100
PIPE 60 L=1000 SP.2,0
G15811-06-90
BEND Ø60-90° SP.2,0
G15811-06-45
BEND Ø60 a 45° SP.2,0
G15831-06-V
VERTICAL RAIN SHELTER Ø60
G15816-06-08
M-F ADAPTER Ø60-80
G15821-08-100
PIPE Ø80 L=1000 SP.2,0
G15831-08-V
VERTICAL RAIN SHELTER Ø80
Maximum length allowed with polypropylene plain tube Ø60
is 4 meters on a straight line. If bends are used, deduct from
max length:
•
1.5 m per each PP 90° bend Ø60 (wide radius)
•
1.0 m per each PP 45° bend Ø60 (wide radius)
We recommend orienting horizontal flue terminal towards the
front of the boiler (see drawing in this page) to avoid flue con
-
densation on the wall of the building.
WARNING: Install a shelter on boiler flue outlet to prevent
rain from dropping into the unit.
If flue system is longer than 4 meters, an adaptor 60M/80F
should be used (code G15816-06-08) to shift to Ø80 terminal.
If Ø80 PP plain tube is used, maximum length extends to 8 m.
EQUIPMENT SET FOR G20 [Natural gas]
Model
Temperature
flue [°C]
Content
CO2
Flue Flow
Rate
[kg/h]
032
84 (93*)
9.2
53.2
034
85
9.2
60.4
050
84
9.1
99.4
070
83
9.4
107.5
EQUIPMENT SET FOR G31 [Liquid propane gas]
Model
Temperature
flue [°C]
Content
CO2
Flue Flow
Rate
[kg/h]
032
84 (93*)
9.6
46.4
034
85
9.6
53.6
050
85
9,9
89,3
070
82
9.6
96.6
If bends are used, deduct from max length:
•
0.7 m for each Ø80 90° bend (wide radius);
•
0.3 m for each Ø80 45° bend (wide radius);
N
ote: It is mandatory to have a hole for flue analysis on stack
pipe, at a max distance of 1 meter from the boiler.
* Temperatures in brackets refer to 00X0 model
Summary of Contents for AQUAKOND AKY
Page 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Page 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Page 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Page 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...