CONDENSATION BOILER
AQUAKOND AKY
15
code HC0048.01GB ed.B-1406
AKY
3.4. ISPESL COMPONENTS
SAFETY, CONTROL AND PROTECTION DEVICES
Component
Code
Model
Description
Hydrometer
ID
PB3204BB06
Manometer class UNI2.5, range 0-4bar
WATTS INDUSTRIES
p
max, ex.
+25% f.s., T=-20/90°C ISPESL-compliant
Limit pressure switch IPMAX PMR/5-R2
Pressure switch p=1-3bar
ITALTECNICA
ISPESL-compliant certificate N° PS/001/10
Inspection well
PIT
PGUA0TT003
Control well L=45mm, fitting 1/2"
WATTS INDUSTRIES
ISPESL-compliant
Control three-way cock RB
403R14
Three-way cock, fitting 1/4",
WATTS INDUSTRIES
T
max, ex
=90°C, P
max, ex
=15bar ISPESL-compliant
Thermometer
TER
PT4A507011
Fitting 1/2" with well
WATTS INDUSTRIES
T=0/120°C precision class UNI 2, ISPESL-compliant
Expansion vessel
VE
13S6001006
10 l. capacity, fitting 3/4",
default charge 0.75bar
WATTS INDUSTRIES
T
max, ex.
=90°C, P
max, ex.
=15bar ISPESL-compliant
Safety valve
VS
527427
Fittings 1/2"Fx3/4"F, adjusted 2,7 bar, diameter 15 mm,
CALEFFI discharge capacity 152.2 kW. Tmax=110°CV
ISPESL APPROVAL CERTIFICATE N°VS/319/00
Safety thermostat
TS
1NT08L
NC terminal of thermostat, opening T=87±4°C
Sensata
T
es
=-20/+180°C,
KEMA certificate 2014531.16
NOTE: Test on Water Circuit
ISPESL standards require that the boiler body is tested at a pressure of 4.5 bars, i.e. one and a half times its maximum working
pressure.
NOTE: Distance between expansion tank and safety valve [only AKY050/070].
According to ISPESL standards, the distance between the vessel centerline and the safety valve centerline is 450 mm.
NOTE: Fuel detection valve [AKY050/070 only].
ISPESL standards
mandatorily require
the installation of a fuel detection valve on appliances over 35 kW. In designing the boiler,
Apen Group envisaged the possibility to add a well for inspecting the fuel detection valve. Relevant kit has the code C09073.
NOTE: Expansion vessel
All boilers include an expansion vessel with 10 l. capacity, pre-loaded at 0.75 bars.
When system capacity exceeds 95-100 litres, an expansion vessel with suitable capacity shall be installed.
Water contents of boilers are summarized in the table below. For information on pipes, see page 16 of this Manual.
WATER CONTENT
Boiler
AKY032 3.5 l
Boiler
AKY034 4.0 l
Boiler
AKY050 6.3 l
Boiler
AKY070 7.0 l
Summary of Contents for AQUAKOND AKY
Page 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Page 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Page 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Page 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...