Finishing the Project
145
VisualArchitect v1.1
CONFIDENTIAL AND PROPRIETARY. COPYRIGHT, AMX LLC, 2006
4.
Press the TAB key (or click in any other cell) to enter the information and update the table with the
various cable and voltage drop information that it provides:
Max Cable Length
(Column C, Rows 4-10): This group of cells shows the total feet of cable
of a particular size that can support the selected equipment.
Total Current Draw
(Column A, Row 6): This cell shows the total current draw for all
devices entered. The System tab shows the total for all pages.
Voltage Drop
(Columns G, H, I - Rows 4-10): This group of cells shows the voltage drop for
a selected cable length and device set. Enter the estimated cable length in the yellow box and
read the voltage drop for the wire gauge at the right. Use a cable gauge that is shown in green.
By default, length is calculated in feet. Click the drop-down menu (in column E) to
change "FEET" to "METERS".
All current draw values are "Worst Case" or Max values as listed in AXPower.txt.