Protected Setup Pages
86
MVP-5200i Modero Viewpoint Widescreen Touch Panel
Calibration Page
The
Calibration
page (FIG. 70) allows you to calibrate the touch panel for accurate button selection.
1.
Press and hold the center button on the navigation wheel for 6 seconds to access the
Calibration
page (see FIG. 54).
2.
Press the crosshairs in turn. If the crosshairs are not touched within ten seconds, the MVP-5200i
will return to the
Protected Setup
page.
3.
The page will read "Calibration Successful. Touch to continue." Touch anywhere on the screen to
return to the
Protected Setup
page.
Always calibrate the panel before its initial use, and after downloading new firmware.
FIG. 70
Calibration page
If the screen is not touched at that point, the device will automatically return to the
Protected Setup
page within 10 seconds.
Summary of Contents for Modero Viewpoint MVP-5200i
Page 28: ...Accessories 20 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 56: ...Configuring Communication 48 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 68: ...Setup Pages 60 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 106: ...Protected Setup Pages 98 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 174: ...Programming 166 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 182: ...Battery Life and Replacement 174 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...
Page 201: ...Appendix 193 MVP 5200i Modero Viewpoint Widescreen Touch Panel ...